Power
Circuit
Breakers
SECTION
2
Installation
DISCONNECTED
Both
primary
and
secondary
contacts
are
disengaged
.
WITHDRAWN
With
the
compartment
door
open
,
the
breaker
can
be
manually
pulled
out
to
the
WITHDRAWN
position
.
At
this
point
the
tracks
are
fully
extended
and
the
breaker
is
completely
out
of
its
compartment
,
ready
for
removal
.
Note
that
the
racking
mechanism
is
not
employed
for
movement
of
the
breaker
between
the
DISCONNECTED
and
WITHDRAWN
positions
.
2
.
Using
the
lifting
wire
provided
,
raise
the
breaker
above
the
elevation
of
the
tracks
.
3
.
Slowly
lower
and
guide
the
breaker
so
that
the
breaker
mounting
pins
drop
into
the
slots
in
the
tracks
.
Remove
the
lifting
wire
.
4
.
Push
the
breaker
into
the
compartment
until
it
reaches
the
stops
.
This
is
the
DISCONNECT
position
.
At
this
point
the
racking
arms
are
positioned
to
engage
the
fixed
racking
pins
in
the
compartment
,
ready
to
begin
the
racking
motion
.
5
.
Push
in
the
inner
rails
and
close
the
compartment
door
.
Insert
the
racking
handle
into
the
racking
screw
opening
in
the
compartment
door
.
By
clockwise
rotation
of
the
handle
,
move
the
breaker
through
the
TEST
position
into
the
CONNECTED
position
;
the
latter
is
indicated
when
the
jackscrew
comes
to
a
solid
stop
.
Breaker
Insertion
1
.
Prior
to
lifting
a
breaker
to
its
intended
compartment
location
,
observe
the
following
precautions
:
Breaker
Removal
1
.
With
the
door
closed
and
latched
,
trip
the
breaker
.
2
.
Insert
the
racking
handle
and
rotate
it
counterclockwise
until
the
breaker
travels
from
CONNECTED
through
TEST
to
the
DISCONNECTED
position
,
as
indicated
by
the
jackscrew
coming
to
a
solid
stop
.
This
operation
should
be
performed
with
the
door
closed
.
3
.
Open
the
compartment
door
and
pull
inner
rails
to
the
extended
position
.
Pull
the
breaker
out
to
the
travel
limit
this
is
the
WITHDRAWN
position
.
4
.
Attach
the
lifting
wire
and
hoist
the
breaker
until
its
mounting
pins
clear
the
track
slots
.
5
.
Swing
the
breaker
forward
until
the
primary
disconnects
clear
the
compartment
and
lower
the
breaker
onto
a
flat
surface
free
of
protrusions
that
could
damage
the
breaker
s
internal
parts
.
PRECAUTIONS
a
.
Check
the
compartment
to
ensure
that
it
is
free
of
foreign
objects
.
b
.
Verify
that
the
breaker
is
the
correct
type
for
that
compartment
.
c
.
Ensure
that
the
breaker
is
OPEN
.
d
.
Apply
a
thin
,
fresh
coat
of
D
50
HD
38
lubricant
to
the
breaker
s
primary
disconnects
.
e
.
Ensure
that
the
racking
cams
on
the
breaker
are
correctly
positioned
for
initial
engagement
with
the
pins
in
the
compartment
.
To
do
this
,
insert
the
racking
handle
and
rotate
it
fully
counter
-
clockwise
.
4
Courtesy of NationalSwitchgear.com

Other manuals for GE AKR-30S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE AKR-30S and is the answer not in the manual?

GE AKR-30S Specifications

General IconGeneral
BrandGE
ModelAKR-30S
CategoryOther
LanguageEnglish

Related product manuals