What to do if my GE Baker Hughes Reuter-Stokes Flame Tracker RS-FS-9006 have a low flame intensity signal during operation?
- LLauren DavisAug 6, 2025
If you are experiencing a low flame intensity signal during operation with your GE Security Sensors, it could be due to several reasons. First, check the squareness of all flanges and pipes of the sensor mount and verify that the sensor has a clear view of the flame, as misalignment can cause this issue. Second, look for any obstructions in the line of sight, such as washers or valves that may restrict the diameter of the sight tube. Finally, condensation on the lens can also cause this problem; reduce the cooling until the condensation clears up and the signal returns to normal.