Introduction
The  Undervoltage  Release  (UVR)  accessory,  shown  in  Figure
1,  can  be  installed in  800–4000  ampere  frame  Power  Break®
II circuit breakers. This  accessory  trips the  circuit  breaker  when
the  input  control  voltage  drops  to  35–60%  of  its  rated  value
and  prevents  an  open  breaker  from  closing  until  the  input
control voltage  is greater than  80%  of the rated  value.
In  addition  to  providing  a  trip  signal  to  the  breaker,  the  UVR
accessory  can  be  set  up  to interact  with  other  Power  Break  II
accessories,  when  used  with  a  MicroVersaTrip  Plus™  or
MicroVersaTrip  PM™  Trip  Unit.  DIP switches  on  the  rear  of
the  breaker  Trip  Unit  can  configure  the  UVR  accessory  to
activate  a  Bell  Alarm–Alarm  Only  accessory  or  a  Bell  Alarm
with  Lockout  accessory  when  a  UVR  trip  occurs.  The  Accessory
Configuration  section  below  describes  how  this  can  be  done.  If
the  breaker  is  equipped  with  a  Power+™  Trip  Unit,  it  is
configured  so  that  only  protection  trips  will  activate  a  Bell
Alarm–Alarm Only or  Bell  Alarm with  Lockout.
The  catalog  numbers  for  the  UVR  for  various  voltage
applications  are  listed in  Table 1.
Figure 1. Undervoltage Release.
Operation
Apply  control  voltage  to  terminals  29  and  30  of  the  ter minal
strip  on the right side  of  the  breaker.  When  the  applied  control
voltage  is above 80%  of the UVR’s  rated  value, the breaker  can
be  closed.  When  the  voltage  drops  to  35–60%  of  the  rated
value, the UVR will trip the breaker.
Catalog
Number
Voltage
Rating 
❿
Peak Inrush
Current, A 
Nominal RMS
Current,  mA
SPUV012DC 12  Vdc 19 300
SPUV024DC 24  Vdc 15 140
SPUV048DC 48  Vdc 7.5 70
SPUV125DC 125  Vdc 3 30
SPUV250DC 250  Vdc 1.5 15
SPUV024AC 24 Vac 15 370
SPUV048AC 48 Vac 7.5 210
SPUV120AC 120  Vac 3 80
SPUV208AC 208  Vac 1.9 60
SPUV240AC 240  Vac 1.5 45
❿
24–240 Vac devices are rated for 50/60 Hz.
❡
Peak inrush current is present for 2–6 ms after activation. This
number is provided so that fuses and supplies can be chosen
appropriately.
Table 1. Catalog numbers and voltages for the Undervoltage Release.
Installation
WARNING:  Before  installing any accessories, turn the  breaker
OFF,  disconnect  it  from  all voltage  sources,  and  discharge  the
charging springs.
AVERTISSEMENT:  Avant  d’installer  toute  accessoire,  mettre
le disjoncteur  en position  OFF,  le déconnecter  de  toute  tension
d’alimentation,  et décharger les  ressorts d’armement.
The  Undervoltage  Release  is  installed  in  the  accessory
compartment  through  the  front  of  the  circuit  breaker  in  the
position  shown  in  Figure  2.
Figure 2. Accessory compartment on front of circuit breaker, with
Undervoltage Release slot indicated.
Power Break
®
 II Circuit Breaker
Accessories
Undervoltage Release
                                                               
GEH–6285C
U
2
dervoltage
Release
Catalog
No
SPUV
12
QAC
29
—
f
ELEC
30
-
MOO
Hati
Peak
isti
Norn
120
V
AC
50
/
60
HZ
3
A
Made
80
mA
USA
<
8
Remove
beforp
ii
accessory
power
"
Stalling
or
removing
Shunt
Trip
or
Shunt
Trip
with
Lockout
Bell
Alarm
with
Lockout
Bell
Alarm
-
Alarm
Only
Undervoltage
Release