Power
Break
®
/
/
Circuit
Breaker
Accessories
Mechanical
interlock
for
Draw
-
Out
Breakers
,
2500
-
4000
A
Frames
Introduction
The
Mechanical
Interlock
accessory
,
catalog
number
SPDOWB
40
and
shown
in
Figure
1
,
can
be
installed
in
2500
-
4000
ampere
frame
Power
Break
®
II
draw
-
out
circuit
breakers
.
This
accessory
is
for
use
only
with
circuit
breakers
,
draw
-
out
substructures
,
and
shutters
with
a
manufacture
date
code
later
than
E
640
=
(
where
E
represents
the
plant
where
manufactured
,
6
is
the
year
,
40
is
the
week
of
that
year
,
and
=
is
the
decade
code
in
this
case
,
the
90
s
)
.
When
two
breakers
in
adjacent
compartments
are
connected
with
an
interlock
rod
,
as
shown
in
Figure
2
,
this
accessory
prevents
the
simultaneous
closing
of
both
breakers
.
When
either
breaker
is
ON
,
the
other
-
will
immediately
trip
if
an
attempt
is
made
to
turn
it
ON
also
.
When
both
breakers
are
OFF
,
either
breaker
may
be
turned
ON
.
However
,
when
one
breaker
is
ON
,
an
attempt
to
close
the
second
breaker
causes
its
closing
springs
to
discharge
without
moving
the
contact
arms
.
An
override
feature
is
provided
in
case
of
a
race
condi
-
tion
(
both
breakers
turned
ON
simultaneously
)
,
so
that
the
breaker
designated
as
primary
turns
ON
and
the
secondary
breaker
trips
.
Either
or
both
circuit
breakers
may
be
CHARGED
at
any
time
,
but
the
interlock
operation
activates
only
when
one
of
the
breakers
is
ON
.
&
Figure
2
.
Mechanical
Interlock
attached
to
Power
Break
II
draw
-
out
circuit
breakers
.
Horizontal
or
Vertical
Connection
The
interlocked
breakers
can
be
mounted
and
con
-
nected
either
vertically
(
one
breaker
above
the
other
)
or
horizontally
(
breakers
mounted
side
by
side
)
.
The
connecting
rod
can
be
installed
in
either
of
two
posi
-
tions
for
the
desired
action
.
All
end
connectors
are
provided
,
so
the
customer
need
only
supply
a
14
-
20
threaded
rod
of
the
appropriate
length
.
Installation
WARNING
:
Before
installing
any
accessories
,
turn
the
breaker
off
,
disconnect
it
from
all
voltage
sources
,
and
discharge
the
charging
springs
.
AVERTISSEMENT
:
Avant
d
installer
tout
accessoire
,
mettre
le
disjoncteur
en
position
OFF
,
le
deconnecter
de
toute
tension
d
alimentation
,
et
decharger
les
ressorts
d
armement
.
EPW
r
/
r
*
o
,
O
'
If
shutters
have
been
installed
in
the
draw
-
out
substruc
-
ture
,
they
must
be
removed
before
the
mechanical
interlock
can
be
installed
.
Reinstall
the
shutters
after
completing
installation
of
the
interlock
.
Figure
1
.
Mechanical
Interlock
accessory
components
.
Courtesy of NationalSwitchgear.com

Other manuals for GE Power Break II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Power Break II and is the answer not in the manual?

GE Power Break II Specifications

General IconGeneral
BrandGE
ModelPower Break II
CategoryCircuit breakers
LanguageEnglish

Related product manuals