Cooling Only
Side Discharge
Condensing Units
Service Manual
Rev. 06-21
UUC112WC*
UUC118WC*
UUC124WC*
UUC130WC*
UUC136WC*
UUC148WC*

Questions and Answers

Summary

Safety Notifications

Maintenance Safety

Covers prohibited actions, warnings, notices, and observations for safe maintenance.

Operation Safety

Details prohibited actions, warnings, and notices for safe unit operation.

Error Codes

Troubleshooting

Fan Motor Not Operating

Diagnostic steps for fan motor failure, including capacitor and wiring checks.

Compressor Not Operating

Troubleshooting guide for compressor inactivity, focusing on capacitor and wiring inspection.

Both Fan Motor and Compressor Not Operating

Troubleshooting for simultaneous fan and compressor failure, checking contactor and switches.

Low Pressure Error (UUC148 WC* unit only)

Troubleshooting guide for low pressure errors, covering refrigerant levels and switch checks.

Overview

This document is a service manual for GE Appliances Cooling Only Side Discharge Condensing Units. The manual covers several models, including UUC112WC*, UUC118WC*, UUC124WC*, UUC130WC*, UUC136WC*, and UUC148WC*.

Function Description:

These units are designed for cooling applications, functioning as outdoor condensing units that discharge air from the side. They are part of a split-system air conditioning setup, requiring an indoor coil for complete operation. The units utilize R410A refrigerant and are available in various capacities to suit different cooling needs.

Important Technical Specifications:

The manual provides detailed specifications for various models, categorized by voltage (115V and 208-230V) and cooling capacity (12k, 18k, 24k, 30k, 36k, and 48k BTU/hr).

For 115V Models:

  • UUC112WCDA (12k BTU/hr):

    • Rated Capacity: 12,000 Btu/hr
    • SEER/EER: 14/12
    • Operating Range: 50-115°F (10-46°C)
    • Voltage/Cycle/Phase: 115/60/1
    • Max Fuse Size: 15 A
    • Min Circuit Amp: 11 A
    • Outdoor Noise Level: 52 dB
    • Fan Speed RPM: 820
    • Outdoor Airflow CFM: 1220
    • Compressor Type: Rotary
    • TXV: Bleed
    • Dimensions (H x W x D): 21.9 x 33.5 x 13.6 in (555 x 850 x 345 mm)
    • Refrigerant: R410A
    • Factory Charge: 4.2 lbs
    • Max Line Length: 82 ft (25 m)
    • Max Height: 33 ft (10 m)
    • AHRI Matching Indoor Coil: Aspen Model C(A,C,E)24A24+TDR
    • CFM with rated coils: 445
    • Liquid | Suction O.D.: 1/4 | 1/2 in
  • UUC118WCDA / UUC118WCDBA (18k BTU/hr):

    • Rated Capacity: 17,500 / 18,000 Btu/hr
    • SEER/EER: 14.5/12 / 14.2/12.2
    • Voltage/Cycle/Phase: 208-230/60/1
    • Max Fuse Size: 15 A
    • Min Circuit Amp: 10 A
    • Outdoor Noise Level: 55 dB
    • Fan Speed RPM: 890
    • Outdoor Airflow CFM: 2012
    • Compressor Type: Rotary
    • TXV: Bleed
    • Dimensions (H x W x D): 27.6 x 36.0 x 15.0 in (702 x 914 x 382 mm)
    • Refrigerant: R410A
    • Factory Charge: 4.7 / 5.1 lbs
    • AHRI Matching Indoor Coil: Aspen Model C(A,C,E)24B44+TDR, ADP Model HE81(6,9)36+TDR
    • CFM with rated coils: 620 / 650
    • Liquid | Suction O.D.: 1/4 | 1/2 in
  • UUC124WCDA / UUC124WCDBA (24k BTU/hr):

    • Rated Capacity: 23,500 / 24,000 Btu/hr
    • SEER/EER: 14.5/12
    • Voltage/Cycle/Phase: 208-230/60/1
    • Max Fuse Size: 15 A
    • Min Circuit Amp: 12 / 11.4 A
    • Outdoor Noise Level: 58 / 59 dB
    • Fan Speed RPM: 880
    • Outdoor Airflow CFM: 2492
    • Compressor Type: Rotary
    • TXV: Bleed
    • Dimensions (H x W x D): 31.9 x 40.0 x 17.5 in (810 x 1015 x 445 mm)
    • Refrigerant: R410A
    • Factory Charge: 6.1 / 6.3 lbs
    • AHRI Matching Indoor Coil: Aspen Model C(A,C,E)24B44+TDR, ADP Model HE81(6,9)36+TDR
    • CFM with rated coils: 727 / 780
    • Liquid | Suction O.D.: 3/8 | 5/8 in

For 208-230V Models:

  • UUC130WCDA / UUC130WCDBA (30k BTU/hr):

    • Rated Capacity: 30,000 Btu/hr
    • SEER/EER: 14.5/12 / 14.5/12.2
    • Voltage/Cycle/Phase: 208-230/60/1
    • Max Fuse Size: 20 A
    • Min Circuit Amp: 14 A
    • Outdoor Noise Level: 58 / 59 dB
    • Fan Speed RPM: 880
    • Outdoor Airflow CFM: 2324
    • Compressor Type: Rotary
    • TXV: Bleed
    • Dimensions (H x W x D): 31.9 x 40.0 x 17.5 in (810 x 1015 x 445 mm)
    • Refrigerant: R410A
    • Factory Charge: 7.3 / 7.5 lbs
    • AHRI Matching Indoor Coil: Aspen Model C(A,C,E)36B44+TDR, ADP Model HE81(6,9)36+TDR
    • CFM with rated coils: 1050 / 1080
    • Liquid | Suction O.D.: 3/8 | 3/4 in
  • UUC136WCDA / UUC136WCDBA (36k BTU/hr):

    • Rated Capacity: 34,000 / 35,000 Btu/hr
    • SEER/EER: 14.5/12 / 14.2/12.2
    • Voltage/Cycle/Phase: 208-230/60/1
    • Max Fuse Size: 25 A
    • Min Circuit Amp: 16 A
    • Outdoor Noise Level: 58 / 59 dB
    • Fan Speed RPM: 890 / 900
    • Outdoor Airflow CFM: 2300
    • Compressor Type: Rotary
    • TXV: Bleed
    • Dimensions (H x W x D): 31.9 x 40.0 x 17.5 in (810 x 1015 x 445 mm)
    • Refrigerant: R410A
    • Factory Charge: 7.3 / 7.7 lbs
    • AHRI Matching Indoor Coil: Aspen Model C(A,C,E)48C34+TDR, ADP Model HE35(6,9)48+TDR
    • CFM with rated coils: 1025 / 1150
    • Liquid | Suction O.D.: 3/8 | 3/4 in
  • UUC148WCDA (48k BTU/hr):

    • Rated Capacity: 46,000 Btu/hr
    • SEER/EER: 14/11.7
    • Voltage/Cycle/Phase: 208-230/60/1
    • Max Fuse Size: 40 A
    • Min Circuit Amp: 26 A
    • Outdoor Noise Level: 60 dB
    • Fan Speed RPM: 900
    • Outdoor Airflow CFM: 2600
    • Compressor Type: Scroll
    • TXV: Bleed
    • Dimensions (H x W x D): 34.25 x 43.31 x 20.79 in (870 x 1100 x 528 mm)
    • Refrigerant: R410A
    • Factory Charge: 8.8 lbs
    • Max Line Length: 98 ft (30 m)
    • Max Height: 50 ft (15 m)
    • AHRI Matching Indoor Coil: Aspen Model C(A,C,E)48C34+TDR
    • CFM with rated coils: 1325
    • Liquid | Suction O.D.: 3/8 | 3/4 in

Usage Features:

The units are designed for cooling-only operation. They feature various settings that can be configured on the Outdoor Unit PCB (UUC136WC*/UUC148WC* Only):

  • Fan Speed Selection (SW1-1 & SW1-3): Allows selection of fan speeds at 800 rpm, 830 rpm, or 900 rpm (default).
  • Power Supply Selection (SW1-2): Configurable for 380V, 3 phase or 220V, 1 phase (default).
  • Condenser Protection Temperature & Recovery Temperature (SW1-4):
    • Default setting: Unit stops if T3 (condenser temperature) exceeds 149°F (65°C) and restarts when T3 drops below 118°F (48°C).
    • Alternative setting: Unit stops if T3 exceeds 154°F (68°C) and restarts when T3 drops below 126°F (52°C).

Maintenance Features:

The manual emphasizes safety notifications for both maintenance and operation.

  • Safety Notifications:

    • Prohibited: Do not pierce or burn, mix refrigerants, modify the unit, or operate with worn wires. Ensure proper ventilation during refrigerant leaks. Disconnect power before maintenance.
    • Warning: Wear safety gear for high installations. Test for leaks before charging. Isolate power for repairs. Maintain a regular schedule for preventive maintenance.
    • Notice: Requires proper earth ground. Do not repair with wet hands. Isolate power before cleaning. All field wiring must conform to codes. Brazing/welding must be done in ventilated areas. Keep fire sources away. Clean with soap and water only. Do not remove fan cover while running.
    • Observed: Check condensate drain outlets. Unit must be installed level and on a supportive surface. Disassembly and refrigerant handling must follow local rules.
  • Troubleshooting: The manual provides detailed troubleshooting flowcharts for common issues:

    • Fan Motor Not Operating: Steps include inspecting wiring, checking the fan capacitor (capacitance values provided for different models), and replacing the fan motor or capacitor.
    • Compressor Not Operating: Steps include inspecting wiring, checking the compressor capacitor (capacitance values provided for different models), and replacing the compressor or capacitor.
    • Both Fan Motor and Compressor Not Operating: Steps include verifying voltage, checking contactor pull-in, and troubleshooting the discharge temperature switch (FT) and high-pressure switch.
    • T3 Condenser Temperature Sensor (UUC136WC/UUC148WC Only):** Troubleshooting involves checking sensor-PCB connection and sensor status (open/closed). For 36/48K models, T3 is connected to a fixed 5KΩ resistor.
    • T5 Discharge Temperature Sensor (UUC136WC/UUC148WC Only):** Troubleshooting involves checking sensor-PCB connection and sensor status (open/closed). T5 resistance at 77°F (25°C) is 50KΩ, and at 95°F (35°C) is 33KΩ.
    • Low Pressure Error (UUC148WC Only):* Troubleshooting involves checking for lack of refrigerant, repairing leaks, charging refrigerant, and checking/replacing the PCB or low-pressure switch. CN17 is the low pressure switch connection.
    • High Pressure Error: Troubleshooting involves checking for excessive refrigerant, recovering/recharging refrigerant, checking the outdoor unit coil, and checking/replacing the PCB or high-pressure switch. CN13 is the high pressure switch connection.
    • Fan Motor Error: Steps include checking DC fan motor wiring, fan driver board for damage, and the CN8 port of the main PCB. Provides details on checking voltage at CN8 pins (1-2: 310V DC, 3-2: 15V DC, 4-2: 0-5V DC, 5-2: 0-5V DC). Fan motor rated voltage is 310VDC, power output 220W, and rated speed 870 RPM.
  • Error Codes (UUC136WC/UUC148WC Only):** The manual lists LED flash patterns on the outdoor unit PCB to indicate specific errors:

    • Green LED on: Normal Operation
    • 1 flash every 5s: High Pressure Error (resets after power cycle if occurs 3 times in 20 mins)
    • 2 flashes every 5s: T3 (Outdoor Unit Heat Exchanger Sensor) Temperature Sensor Error
    • 3 flashes every 5s: Over Current Error (Reserved for 36/48K models)
    • 4 flashes every 5s: Power Phase Error (Only for three-phase models)
    • 5 flashes every 5s: T5 (Compressor Discharge Temperature Sensor) Temperature Sensor Error
    • 6 flashes every 5s: Low Pressure Error (48K model only, resets after power cycle if occurs 3 times in 20 mins)
    • 7 flashes every 5s: Fan Motor Error
  • 3rd Party Coil Matching: For customers installing with AHRI approved 3rd party coils, the unit is eligible for standard 7-year compressor/5-year parts limited warranty and 10-year compressor/parts standard registered limited warranty. Registration is available at haierappliances.com/support/register-ductless. AHRI certification for matched systems can be verified at ahridirectory.org/Search/SearchHome.

GE UUC136WCDA Specifications

General IconGeneral
BrandGE
ModelUUC136WCDA
TypeWindow Air Conditioner
Voltage115V
Cooling Area550 sq. ft.
Installation TypeWindow
Remote ControlYes
Programmable TimerYes
Number of Cooling Speeds3
Number of Fan Speeds3
Filter TypeWashable
ColorWhite
Noise Level54 dB
RefrigerantR32
FeaturesEnergy Saver Mode

Related product manuals