EasyManua.ls Logo

GEA Bock HGX34e/380-4 - Page 23

Default Icon
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D
GB
F
E
I
Ru
23
96178-06.2015-DGbFEIRu
RelaypositionINT69G
B2 12 14 11
Fig.26
5.10 Function test of the trigger unit INT69 G
Beforecommissioning,aftertroubleshootingormakingchangestothecontrolpowercircuit,check
thefunctionalityofthetriggerunit.Performthischeckusingacontinuitytesterorgauge.
5| Electrical connection
Gauge state Relay position
1.
Deactivatedstate 11-12
2.
INT69Gswitch-on 11-14
3.
RemovePTCconnector 11-12
4.
InsertPTCconnector 11-12
5.
Resetaftermainson 11-14
5.11 Start unloader
To avoid current peaks during the starting phase we recommend using the GEA Bock-ESS soft
startingdevice(ElectronicSoftStart).Referto"Accessories"forfurtherinformation.

Related product manuals