DT109A / DT107A / DT106A / DT105A / DT104A
AUTO-TUNE PID TEMPERATURE CONTROLLER
Attention, Risk of, High Voltage, Double / Reinforced NOT CE Mark
Danger, Warning Risk of Electric Shock Insulation Litter
TECHNICAL SPECIFICATION
Dimensions : DT109:96x96, DT107:72x72, DT105/DT106:48x96, DT104:48x48mm
Panel Cut-out : DT109:91x91, DT107:68x68, DT105/DT106:93,5x45,5, DT104:45,5x45,5mm
Display : 4 Digits 7 Segment (PV), 4 digits 7 Segment (SV)
Sensor Type : J,K,T,S,R type T/C, Pt100 selectable
Measuring Scale : -100 .. 600
o
C, J type T/C, (Inpt=J), -100 .. 1300
o
C, K type T/C, (Inpt=k)
-100 .. 400
o
C, T type T/C, (Inpt=t), 0 .. 1750
o
C, S type T/C, (Inpt=S)
0 .. 1750
o
C, R type T/C, (Inpt=r), -100 .. 600
o
C, Pt100, (Inpt=Pt)
-99.9 .. 600.0
o
C, Pt100, (Inpt=Pt.0)
Resolution : ± 1
o
C or ± 0.1
o
C
Accuracy : ± 0.3 % (Over full scale)
Control Form : ON-OFF or P, PI, PD, PID - selectable
Out Output : Relay (NO + NC), 250VAC, 2A, Resistive load, (optional SSR)
Alarm Output : Relay (NO + NC), 250VAC, 2A, Resistive load, (only NO for DT104)
Heat SET : Lower Limit .. Upper Limit
o
C (H.Set)
Alarm SET : AL.tY = Abs,-Abs; Lo.L .. UP.L
o
C (A.Set)
AL.tY = rel, -rel, bnd, -bnd, bn.i, -bn.i; -100 .. +100 / -10.0 .. +10.0 (Pt.0)
Heat Hysteresis : 0 .. 50 / 0.0 .. 5.0
o
C (H.Hys); PID is active if set to 0
Alarm Hysteresis : 1 .. 50 / 0.1 .. 5.0
o
C (A.Hys)
Proportional Band : 1 .. 130
o
C (Pb.C)
Integral Time : 0 .. 30,0 min. (OFF if set to 0)
Derivative Time : 0.. 10,0 min. (OFF if set to 0)
Control Period : 4 .. 200 sec. (Ct)
Offset : -100..+100
o
C / -10.0 .. +10.0
o
C (oFFS)
Heating/Cooling : Selectable (only ON-OFF control form is active for cooling)
Cold. Junc. Comp. : 0 .. 50
o
C (T/C)
Line Comp. : 10 Ohm max. (3 wire Pt100)
Sensor Failure : ALARM output is always OFF, OUT output is active according to P.Err and
Ct parameters in case of sensor failure, measurement out of range or
hardware fails to measure input signal (OUT output is OFF if Perr is 0)
Supply Voltage : 100..240VAC, 50-60Hz or 24VDC/AC (isolation voltage: 40VAC max.)
Power Consumption : < 8VA
Humidity : 80% up to 30
o
C, then linearly decreases to 50% at 50
o
C (non-condensing)
Altitude : < 2000 m
EMC : EN 61000-6-1, EN 61000-6-3 (Only light industrial environment)
Safety : EN 61010-1; Pollution degree 1, measurement category I, (Only light industrial
environment, double/reinforced isolated, non-conductive pollution environment)
Protection Class : IP20; according to EN 60529
Operation Temp. : 0 .. 50
o
C
Storage Temperature : -10
o
C .. 60
o
C (no icing)
Weight : < 0.5 kg
Torque for screwing : Max. 0.5 N.m
WARNING :
if 2 wire Pt100 is used, connect compensation lead
to measuring lead: (DT109 / DT105 / DT106:17-18,
DT107: 13-14, DT104: 10-11)
no: normally open
nc: normally closed