OPERATING DATA
KW RATING (LP/NG) 130
ENGINE SIZE 6.8 Liter V-10
GENERATOR OUTPUT VOLTAGE/KW - 60Hz LP AMP NG AMP CB Size
120/240V, 1-phase, 1.0 pf
120/208V, 3-phase, 0.8 pf
120/240V, 3-phase, 0.8 pf
277/480V, 3-phase, 0.8 pf
130
130
130
130
542
451
391
195
117
122
122
122
488
423
367
183
600
500
450
225
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208-240 3-phase
480V 3-phase
270
320
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)
Exercise cycle
25% of rated load
50% of rated load
75% of rated load
100% of rated load
For Btu content, multiply ft
3
/hr x 2520 (LP) or ft
3
/hr x 1000 (NG)
Natural Gas
(ft
3
/hr.)
135
482
927
1292
1786
Propane
(gal/hr.) (ft
3
/hr.)
1.4 54.5
5.3 193
10.3 373
14.3 520
19.8 719
ENGINE COOLING
Air flow (inlet air including alternator and combustion air) ft
3
/min.
System coolant capacity US gal.
Heat rejection to coolant BTU/hr.
Max. operating air temp. on radiator °C (°F)
Max. ambient temperature °C (°F)
6,450
4.5
496,000
60 (150)
50 (140)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz cfm 336
SOUND EMISSIONS IN DBA
Exercising at 7 meters
Normal operation at 7 meters
65
75
EXHAUST
Exhaust flow at rated output 60 Hz cfm
Exhaust temp. at muffler outlet ºC (°F)
1,119
521 (970)
ENGINE PARAMETERS
Rated synchronous RPM 60 Hz 2970
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration
3% for every 10 °C above - °C
1.65% for every 10 °F above - °F
Altitude Deration
1% for every 100 m above - m
3% for every 1000 ft. above - ft.
25
77
183
600
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a
reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with
ISO-3046-1. Design and specifications are subject to change without notice.
kW rating is based on LPG Fuel and may derate with natural gas.
Generac
®
Standby Generator - 130 kW
®