Details of function

Control input function
• When function setting is "Operation/Stop" mode 1
Function setting External input Input signal Command
46—00 Terminal
Off → On Operation
On → Off Stop
Operation
Stop
Remote controller
On
Off
Indoor unit
On
Input
NOTES:
• The last command has priority.
• The indoor units within the same remote controller group operates in the same mode.
• When function setting is "Forced stop" mode
Function setting External input Input signal Command
46—02 Terminal
Off → On Forced stop
On → Off Normal
On
Off
Forced stop
Normal
Operation
Stop
Remote controller
On On
Indoor unit
On
Input
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the re-
mote controller is restricted.
• When forced stop function is used with forming a remote controller group, connect the same
equipment to each indoor unit within the group.
- 148 -
11-1. Compact cassette type, Mini duct type, Slim duct type, and Medium static pressure
duct type
11. External input and output
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE