3) Ceiling height (for Compact cassette type and Ceiling type only)
Select the appropriate ceiling height according to the place of installation.
Function number Setting value Setting description Factory setting
20
00 Standard
01 High ceiling
For the specific height for each setting value, refer to “Installation space” in Chapter 3. "Dimensions"
on page 22.
In case of cassette type models:
The ceiling height values are for the 4-way outlet. Do not change this setting in the 3-way outlet
mode.
7,000 or 9,000 Btu/h models cannot be installed in high ceilings.Do not change this setting.
4) Static pressure (for Medium static pressure duct type only)
Select the appropriate static pressure according to the installation conditions.
Function number Setting value Setting description Factory setting
21
00 Normal
01 High static pressure 1
02 High static pressure 2
03 High static pressure 3
5) Outlet directions (for Compact cassette type only)
Select the appropriate number of outlet directions according to the installation conditions.
Function number Setting value Setting description Factory setting
22
00 4-way
01 3-way
- 265 -
14-5. Function details
14. Function settings
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the General AUXG07KVLA and is the answer not in the manual?

General AUXG07KVLA Specifications

General IconGeneral
BrandGeneral
ModelAUXG07KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals