¢ Indoor unit: 9,000 Btu/h
Cooling
Pipe length
m 2.5 5 10 15 20 25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15 — — — 0.956 0.942 0.928
10 — — 0.977 0.963 0.950 0.936
5 — 0.992 0.985 0.971 0.957 0.943
2.5 0.996 0.996 0.989 0.975 0.961 0.947
0 1.000 1.000 0.993 0.979 0.965 0.951
Indoor unit is lower
than outdoor unit *2
-2.5 1.000 1.000 0.993 0.979 0.965 0.951
-5 — 1.000 0.993 0.979 0.965 0.951
-10 — — 0.993 0.979 0.965 0.951
-15 — — — 0.979 0.965 0.951
Heating
Pipe length
m 2.5 5 10 15 20 25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15 — — — 0.977 0.958 0.939
10 — — 0.993 0.977 0.958 0.939
5 — 1.000 0.993 0.977 0.958 0.939
2.5 1.000 1.000 0.993 0.977 0.958 0.939
0 1.000 1.000 0.993 0.977 0.958 0.939
Indoor unit is lower
than outdoor unit *2
-2.5 0.998 0.997 0.991 0.975 0.956 0.937
-5 — 0.995 0.988 0.972 0.954 0.934
-10 — — 0.983 0.967 0.949 0.930
-15 — — — 0.962 0.944 0.925
¢ Indoor unit: 12,000 Btu/h
Cooling
Pipe length
m 2.5 5 10 15 20 25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15 — — — 0.937 0.912 0.888
10 — — 0.970 0.944 0.919 0.896
5 — 0.992 0.978 0.952 0.927 0.903
2.5 0.996 0.996 0.982 0.956 0.930 0.907
0 1.000 1.000 0.986 0.960 0.934 0.910
Indoor unit is lower
than outdoor unit *2
-2.5 1.000 1.000 0.986 0.960 0.934 0.910
-5 — 1.000 0.986 0.960 0.934 0.910
-10 — — 0.986 0.960 0.934 0.910
-15 — — — 0.960 0.934 0.910
Heating
Pipe length
m 2.5 5 10 15 20 25
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
15 — — — 0.977 0.958 0.938
10 — — 0.993 0.977 0.958 0.938
5 — 1.000 0.993 0.977 0.958 0.938
2.5 1.000 1.000 0.993 0.977 0.958 0.938
0 1.000 1.000 0.993 0.977 0.958 0.938
Indoor unit is lower
than outdoor unit *2
-2.5 0.998 0.997 0.991 0.975 0.956 0.936
-5 — 0.995 0.988 0.972 0.953 0.933
-10 — — 0.983 0.967 0.949 0.929
-15 — — — 0.962 0.944 0.924
- 417 -
7-1. Model: AOHG36KBTA5
7. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOHG36KBTA5
OUTDOOR UNIT
AOHG36KBTA5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the General AUXG07KVLA and is the answer not in the manual?

General AUXG07KVLA Specifications

General IconGeneral
BrandGeneral
ModelAUXG07KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals