SHERLOCK 402
REFRIGERANT GAS LEAK MONITORING AND ALARMING SYSTEM
TYPICAL MACHINE ROOM INSTALLATION
SHER402 P/N 60-0102-00; SHER402-R P/N 60-0102-ZN; SHER402-MB 60-0102-MB 09-10-19
The SHERLOCK 402 (SHER402) Monitoring System
was designed to monitor up to four SHERLOCK Refrigerant
Gas Sensors, activating up to two alarms based upon
user defined alarm level setpoints. The SHERLOCK 402
is compliant with ASHRAE 15-2019 and Mechanical Code
requirements for refrigerant gas monitoring.
NEMA 1 Compliant Enclosure - This enclosure is
intended for indoor use only primarily to provide a degree
of protection against contact with the enclosed equipment.
The enclosure is not designed to provide protection from
water or to be placed in a hazardous environment. Mount
only in Pollution Level 2 environments, ie. environmentally
controlled offices, control rooms, or environmentally con-
trolled machine rooms.
Power Input 85 - 240V AC, 50/60 Hz, 2.5 Amp
Inputs Up to 4 Sherlock Sensors: Cmos, Ir
or
Up to three Sherlock Sensors and
One Oxygen Deprivation Sensor
Outputs Six (6) SPDT, 250VAC / 30V DC,
5.0 amp relays, Two (2) relays each,
Level 1, 2 & System.
Auxiliary 12V DC Output
Optional: Auxilliary (Zone cutoff) relays (SHER402-R)
Optional: Modbus RS485 RTU Communications (-MB)
Setback 24 Hour Time Clock
Two Dry Contact Digital Inputs
Alarms Two Alarm Levels, One Fault Level,
Two SPDT Relay per Level, Fuse
On Common Terminal. One relay on
each alarm level can be silenceable
when in alarm. Zone isolation alarm
relays can activate at either level.
Operating Environment
Temperature 32°F To 122°F (0°C To 50°C)
Humidity 0 To 95% RH Non-condensing
Display 2 Line By 20 Character alphanumer-
ic Backlighted LCD display
Keypad 5 Tactile Pushbuttons: Scroll Up,
Scroll Down, Alarm Silent/Clear,
Select/Edit/Change, Exit
Alarm Indicators
Display Name And Current Reading Of
Alarming Sensor
Buzzer Built-in Piezo-electric, 90db @10ft,
Silenceable
Optional Strobe, Factory Mounted on Unit
Listings ETL, Conforms to UL Std. 61010-1
CAN/CSA C22.2 Std. No. 61010-1
Warranty 15 Month Limited
GENESIS INTERNATIONAL, INC.
Nema/IP Size Electrical Pollution
Model # Rating Inches (mm) Category Protection
SHER402 1 12 x 9.5 x 5 II 2
(305 x 241 x 127)
SHE RLOCK
INFRARED
TM
GENESIS INTERNATIONAL INC.
SENSOR for REFRIGERANT GAS
104 0 F ox Chas e Indu stria l D r. A rnold , M O. 6 3010
SENSOR A
POWER LIGHT
SE NSOR M ODU LE
SH E
R
L
OC K
SHE RLOCK
INFRARED
TM
GENESIS INTERNATIONAL INC.
SENSOR for REFRIGERANT GAS
104 0 F ox Chas e Indu stria l D r. A rnold , M O. 6 3010
SENSOR B
INFRARED SENSORS OPTIONAL
EXIT
SELECT
CHANGE
PRESS TO
SILENCE
ACTIVE
ALARM
SENSOR
B
SENSOR
A
SENSOR
C
SENSOR
D
SENSOR
F
SENSOR
E
ALARM
SILENCED
WHEN LIT
SENSOR
H
SENSOR
G
ALARM ACTIVE WHEN LIT
REFRIGERANT GAS
MONITORING SYSTEM
SENSOR ALARM STATUS
POWER LIGHT
SE NSOR M ODU LE
SH E
R
L
OC K
POWER LIGHT
SE NSOR M ODU LE
SH E
R
L
OC K
POWER LIGHT
SE NSOR M ODU LE
SH E
R
L
OC K
SHE RLOCK
INFRARED
TM
GENESIS INTERNATIONAL INC.
SENSOR for REFRIGERANT GAS
104 0 F ox Chas e Indu stria l D r. A rnold , M O. 6 3010
SENSOR C
SHE RLOCK
INFRARED
TM
GENESIS INTERNATIONAL INC.
SENSOR for REFRIGERANT GAS
104 0 F ox Chas e Indu stria l D r. A rnold , M O. 6 3010
SENSOR D
Question and Answer IconNeed help?

Do you have a question about the GENESIS INTERNATIONAL SHERLOCK 402 and is the answer not in the manual?

Summary

SHERLOCK 402 System Overview

System Description

Designed to monitor up to four refrigerant gas sensors, activating up to two alarms.

NEMA 1 Compliant Enclosure

Enclosure intended for indoor use, providing protection against contact with enclosed equipment.

System Features and Specifications

Details power input, sensor inputs, outputs, operating environment, and alarm indicators.

Alarm and Relay Configuration

Alarm Level Settings

Allows setting unique Level 1 and Level 2 alarm setpoints with programmable delays.

Alarm Relay Contacts

Explains SPDT relay outputs for alarm levels and system alarms, with silencing options.

System Monitoring and Options

Covers sensor open monitoring, setback alarms, and optional auxiliary relays/Modbus.

Wiring Diagrams and Recommendations

Illustrates input and output wiring schematics and sensor wiring recommendations.

Overview

The SHERLOCK 402 (SHER402) Monitoring System is a device designed for refrigerant gas leak monitoring and alarming. It is compliant with ASHRAE 15-2019 and Mechanical Code requirements for refrigerant gas monitoring.

Function Description

The SHERLOCK 402 monitors up to four SHERLOCK Refrigerant Gas Sensors. It activates up to two alarms based on user-defined alarm level setpoints. The system constantly monitors the wiring to the sensors, and if communication is lost, an "OPEN" message appears on the display, and alarms activate. The device also includes a SETBACK feature, allowing for alternate alarm conditions based on a secondary Alarm Setpoint and Delay. This can be triggered by a dry contact closure (e.g., air flow switch, sail switch, timer switch) or on a daily schedule.

Important Technical Specifications

Enclosure:

  • Type: NEMA 1 Compliant Enclosure.
  • Intended Use: Indoor use only, primarily to protect against contact with enclosed equipment. Not designed for protection from water or hazardous environments.
  • Mounting Environment: Pollution Level 2 environments (e.g., environmentally controlled offices, control rooms, machine rooms).
  • Dimensions: 12 x 9.5 x 5 inches (305 x 241 x 127 mm).
  • Electrical Pollution Category: II.
  • Protection: 2.

Power:

  • Input: 85 - 240V AC, 50/60 Hz, 2.5 Amp.
  • Auxiliary Output: 12V DC.

Inputs:

  • Up to 4 Sherlock Sensors (CMOS, IR).
  • Up to 3 Sherlock Sensors and 1 Oxygen Deprivation Sensor.
  • Setback: 24 Hour Time Clock, Two Dry Contact Digital Inputs.

Outputs:

  • Relays: Six (6) SPDT, 250VAC / 30V DC, 5.0 amp relays. Two (2) relays each for Level 1, Level 2, and System alarms.
  • Alarm Relays: Two fused SPDT relay outputs for each of the two alarm levels, and a system alarm relay.
    • Level 1 alarm activates K1A and K1B relays.
    • Level 2 alarm activates K2A and K2B relays.
    • System alarm activates 3A and 3B relays.
    • Relays K1B, K2B, and 3B can be silenced.
    • Alarm relays can be configured as "Energized to Alarm" or "De-Energized to Alarm," Common-Normally Open (C-NO) or Common-Normally Closed (C-NC).
  • Optional Auxiliary Relays (SHER402-R): Zone isolation alarm relays (ZA - Sensor A Zone, ZB - Sensor B Zone, ZC - Sensor C Zone, ZD - Sensor D Zone). Each can be programmed to activate by Level 1 or Level 1 & 2 alarm.
  • Optional Modbus RTU (SHER402-MB): RS485 output for communication with a BAS.

Operating Environment:

  • Temperature: 32°F to 122°F (0°C to 50°C).
  • Humidity: 0 to 95% RH Non-condensing.

Sensor Wiring Recommendations:

  • Solid State Sensor: Belden 8443, 3-22 AWG, twisted, stranded.
  • Infrared Sensor: Belden 8770, 3-18 AWG, shielded, twisted.
  • The SHERLOCK 402 can accommodate up to 4 sensors (CMOS or IR) wired to any sensor input. The O2 sensor can only be wired to the Sensor "A" input.

Usage Features

Alarm Level Settings:

  • Unique Level 1 and Level 2 Alarm Setpoints can be set for up to 4 sensors.
  • Programmable Delay: 0 to 120 minutes for alarm activation. Sensor readings must exceed the setpoint for the programmed duration.
  • Alarm Clearing: Can be programmed to clear automatically when the sensor reading drops below the setpoint (UNLATCHED) or require manual reset (LATCHED).

Alarm Indication:

  • Logging: Alarms are logged, storing the last 32 events, including which sensor went into/out of alarm and when.
  • Visual: An LED for the alarming sensor on the front panel will light.
  • Audible: An on-board beeper will sound (90db @10ft, silenceable).
  • Display: The display will show the activated alarm level.
  • Optional Strobe: Factory-mounted strobe available.

Display:

  • Type: 2 Line By 20 Character alphanumeric Backlighted LCD display.
  • Alarm Display: Shows the name and current reading of the alarming sensor.

Keypad:

  • Buttons: 5 Tactile Pushbuttons: Scroll Up, Scroll Down, Alarm Silent/Clear, Select/Edit/Change, Exit.

Maintenance Features

System Sensor Open Monitoring:

  • The SHERLOCK 402 continuously monitors sensor wiring. If a sensor loses communication, "OPEN" will appear on the display, alarms will activate, and the condition will be logged.

Warranty:

  • 15 Month Limited.

Listings:

  • ETL, Conforms to UL Std. 61010-1.
  • CAN/CSA C22.2 Std. No. 61010-1.