-1-
Instruction Manual
GEYA ELECTRICAL CO.,LTD
Add:Wenzhou Brige Industrial Zone,Beibaixiang Town,
Yueqing,Zhejiang,China 325603
Mobile:0086-13567770207
E-mail:sale@cngeya.com
Web:www.geya.net
Voltage / Current Protector GPS8-05
General
Applications
-Overvoltage ,undervoltage and overcurrent protection for household
equipment.
Function Features
-Voltage / current monitoring and protection.
-Special metering chips are used to detect voltage, current, electricity, and power.
-Double bus wiring design stronger ability.
-Over / under voltage value and over-current value can be set.
-Self reset after fault.
-Digital display voltage, current value, fault status can be displayed by LED.
-1-MODULE,DIN rail mounting.
Model and connotation
Technical parameters
Rated operational current
OFF,230V~300V
45~65Hz
AC220V(L-N)
1%
Rated supply voltage
Rated supply frequency
Over voltage operation value
Over/under voltage action delay
Reset time
Power- up delay
Measurement error
-20 ~ +60
-35℃ ~ +75
Din rail EN/IEC 60715
IP40 for front panel/IP20 terminals
any
82 36 68mm× ×
Operating temperature
Storage temperature
Mounting/DIN rail
Protection degree
Operating position
Overvoltage cathegory
Pollution degree
Dimensions
Weight
135g
Burden
AC max.3VA
GPS8-05
Function
Over voltage, under voltage and over current
0.1s~10s
140V~210V,OFF
Under voltage operation value
Over current operation value
Over current action delay
Functions Diagram
TpPower- up delay(2~600s)
TrReset delay time(2~900s)
TuOver/under voltage fault action time(0.1~10s)
TcOvercurrent fault action time(2~600s)
U
LED:
<Tu
Tp
Tr
Tr
I
LED:
LED: >I
Tp
Tr
LED: >U
LED: <U
I
>
Panel Diagram
Power open and close
indicator
Over voltage indicator
Under voltage indicator
Over current indicator
Operating voltage value
Operating current value
32A ,40A,50A,63A,80AAC1
1~32A,40A ,50A,63A ,80A
1×10
1×10
Mechanical life
Electrical life(AC1)
4
GPS8
GPS8 Series
Design number
U:upper incoming line
D:lower incoming line
Incoming line mode
05
Tu Tu
<Tu
Tc
Operation voltage range
80V~400V(L-N)
2s~600s
2s~600s
2s~900s
Parameter setting
Parameter
Range Step value Factory settings
Over voltage value
OFF,230V~300V
275V1V
Under voltage value
140V~210V,OFF
175V1V
Over current value
OFF,1A~32/40/50/63A
32A/40/50/63A0.1A
Over current action delay
2s~600s 5s1s
Reset time
2s~900s 30s1s
Fault reset
ON-OFF ON
Power on delay time
2s~600s 5s1s
Over voltage recovery value
225V~295V 265V1V
Under voltage recovery value
145V~215V 180V1V
Voltage fault action time
0.1s~10s 0.5s0.1s
M
Press and hold the setting key for 3 seconds to enter the
setting. After modifying the setting, press and hold for 3
seconds to save the setting.
Used to increase the value when setting parameters.
1.Used to reduce the value when setting parameters.
2.After exiting the setting, it can be used to manually turn
on or off the load.
3.If the automatic fault reset function is turned off, this button
can be used for manual reset when the fault occurs.
G P S8- 05 6 3A
N
N
IN
>I
<U
>U
M
>I
<U
>U
M
NOTE:
In the power off state, press and hold , and then power on again
to restore the factory settings.
GPS3-05 63
A
LCD backlight time
10s~900s,ON
1s
60s

Questions and Answers: