Chapter 5 Parameters
_
VFD-E Series
5-80 Revision August 2006, 01EE, SW--PW V1.03/CTL V2.03
Group 8: Special Parameters
08.00 DC Braking Current Level Unit: 1
Settings 0 to 100% Factory Setting: 0
 This parameter sets the level of DC Braking Current output to the motor during start-up and
stopping. When setting DC Braking Current, the Rated Current (Pr.00.01) is regarded as
100%. It is recommended to start with a low DC Braking Current Level and then increase until
proper holding torque has been achieved.
08.01 DC Braking Time during Start-up Unit: 0.1
Settings 0.0 to 60.0 sec Factory Setting: 0.0
 This parameter determines the duration of the DC Braking current after a RUN command.
When the time has elapsed, the AC motor drive will start accelerating from the Minimum
Frequency (Pr.01.05).
08.02 DC Braking Time during Stopping Unit: 0.1
Settings 0.0 to 60.0 sec Factory Setting: 0.0
 This parameter determines the duration of the DC Braking current during stopping. If stopping
with DC Braking is desired, Pr.02.02 Stop Method must be set to 0 or 2 for Ramp to Stop.
08.03 Start-Point for DC Braking Unit: 0.01
Settings 0.00 to 600.0Hz Factory Setting: 0.00
 This parameter determines the frequency when DC Braking will begin during deceleration.
Run/Stop
ON
OFF
01.05
08.03
Output Frequency
Minimum Output
Frequency
Start-Point for
DC Braking
Time during
Stopping
DC Braking Time
during Stopping