Chapter 5 Parameters
_
VFD-E Series
5-108 Revision August 2006, 01EE, SW--PW V1.03/CTL V2.03
Settings Function Description
13 Counter Reset
When active, the counter is reset and inhibited. To enable
counting the input should be OFF. Refer to Pr.03.05 and 03.06.
14 External Fault
Parameter value 14 programs one of the Multi-function Input
Terminals MI7 a MI12 (Pr.11.06~Pr.11.11) to be External Fault
(E.F.) inputs.
15
PID function
disabled
When an input ON with this setting is ON, the PID function will be
disabled.
16 Output Shutoff Stop
AC motor drive will stop output and the motor free run if one of
these settings is enabled. If the status of terminal is changed, AC
motor drive will restart from 0Hz.
17
Parameter lock
enable
When this setting is enabled, all parameters will be locked and
write parameters is disabled.
18
Operation
Command
Selection (Pr.02.01
setting/external
terminals)
ON: Operation command via Ext. Terminals
OFF: Operation command via Pr.02.01 setting
Pr.02.01 is disabled if this parameter value 18 is set. See the
explanation below this table.
19
Operation
Command
Selection (Pr 02.01
setting/Digital
Keypad)
ON: Operation command via Digital Keypad
OFF: Operation command via Pr.02.01 setting
Pr.02.01 is disabled if this parameter value 19 is set. See the
explanation below this table.
20
Operation
Command
Selection (Pr 02.01
setting/
Communication)
ON: Operation command via Communication
OFF: Operation command via Pr.02.01 setting
Pr.02.01 is disabled if this parameter value 20 is set. See the
explanation below this table.
21 Forward/Reverse
This function has top priority to set the direction for running (If
“Pr.02.04=0”)
22
Source of second
frequency
command enabled
Used to select the first/second frequency command source. Refer
to Pr.02.00 and 02.09.
ON: 2nd Frequency command source
OFF: 1st Frequency command source