Chapter 5 Parameters
_
VFD-E Series
Revision August 2006, 01EE, SW--PW V1.03/CTL V2.03 5-31
accelerate from start-up to 60 Hz and to decelerate from 60Hz to 1.0Hz is in this case 9.83
seconds. ((60-1) * 10/60=9.83secs).
01.00
01.09
01.11
01.10 01.12
Frequency
Time
Accel. Time
Decel. Time
The definition of
Accel./Decel. Time
Max. output
Frequency
setting
operation
frequency
Min. output
frequency
01.05
Resulting
Resulting
Accel. Time
Decel. Time
Resulting Accel./Decel. Time
0 Hz
01.13 aJog Acceleration Time Unit: 0.1/0.01
Settings 0.1 to 600.0/0.01 to 600.0 sec Factory Setting: 1.0
01.14 aJog Deceleration Time Unit: 0.1/0.01
Settings 0.1 to 600.0/0.01 to 600.0 sec Factory Setting: 1.0
01.15 aJog Frequency Unit: 0.01
Settings 0.10 to Fmax (Pr.01.00)Hz Factory Setting: 6.00
 Only external terminal JOG (MI3 to MI9)can be used. When the Jog command is “ON”, the
AC motor drive will accelerate from Minimum Output Frequency (Pr.01.05) to Jog Frequency
(Pr.01.15). When the Jog command is “OFF”, the AC motor drive will decelerate from Jog
Frequency to zero. The used Accel/Decel time is set by the Jog Accel/Decel time (Pr.01.13,
Pr.01.14).
 Before using the JOG command, the drive must be stopped first. And during Jog operation,
other operation commands are not accepted, except commands via the FORWARD,
REVERSE and STOP keys on the digital keypad.