Chapter 5 Parameters
VFD-E Series
5-36 Revision August 2006, 01EE, SW--PW V1.03/CTL V2.03
RUN
STOP
RUN
STOP
Frequency
Frequency
Time
Time
output
frequency
output
frequency
motor
speed
motor
speed
operation
command
operation
command
stops according to
decel eration time
free run to stop
ramp to stop and free run to stop
EF
Frequency
Frequency
frequency output
motor
speed
EF
operation
command
stops according to
decel eration time
When Pr.02.02 is set to 2 or 3
frequency
output
free run to stop
operation
command
When Pr.02.02 is set to 0 or 1
motor
speed
02.03
PWM Carrier Frequency Selections
Unit: 1
115V/230V/460V Series
Power 0.25 to 15hp (0.2kW to 11kW)
Setting Range 1 to 15 kHz
Factory Setting 8 kHz
This parameter determines the PWM carrier frequency of the AC motor drive.
1kHz
8kHz
15kHz
Carrier
Frequency
Acoustic
Noise
Electromagnetic
Noise or leakage
current
Heat
Dissipation
Current
Wave
Significant
Minimal
Significant
Minimal
Minimal
Significant
Minimal
Significant