Instruction Manual V1 - 06/2014
FEATURES
ZEOS AS
Analogue Addressable Fire Detector
with Smart Addressing
The ZEOS-AS series of Analogue Addressable
Detectors have been designed to be fully compatible
with Global Fire Equipment’s range of intelligent
control panels, JUNIOR and JUNO NET.
The ZEOS-AS series detectors must always be
connected to a compatible GFE Analogue Addressable
Fire Alarm Control Panel. The installation must be in
compliance with the control panel’s system
installation manual.
GFE’s ZEOS-AS series is compliant to EN54-5 and EN54-
7 and consists of: combined photoelectric smoke and
heat/ temperature detectors. All units are supplied
with a short-circuit loop isolator.
The ZEOS-AS range of fire detectors is not addressed
using a D.I.L. switch, it uses instead GFE’s propritary
Smart Addressing Mechanism (SAM). The address can
be set using GFE’s analogue device programmer or
alternatively, when used in conjuction with GFE’s
range of Inteligent Analogue Addressable Fire
Detection Panels, GFE’s automatic address setting
mode ASET.
WARNINGS
To prevent detector contamination and subsequent
invalidation of warranty, the smoke detector head
must remain with its protective cover fitted, until the
area covered is clean and dust free. Detectors are
intended for ceiling and wall mounting and should
always be installed in accordance with local Fire
Authority recomendations and regulations.
Do not install the detector head until the area is
thoroughly cleaned of construction debris, dusts, etc.
Please refer to the control panel’s installation manual
regarding the maximum number of detectors installed
on the same loop.
CAUTION: Do not attempt to disassemble the
detector. This is a sensitive device and is not intended
to be open for servicing by users. Opening the
detector head will void the warranty.
DO NOT PAINT DETECTOR HEAD
Dual LEDs for 360º visibility
Advanced detection and
communication protocols
Easy installation and maintenance
Sleek low-profile housing
Durable sensor head,
no need for replacement
SMD circuit board design.
High quality and reliability guaranteed
Global Fire Equipment S.A. declares that this product is free from defects in materials and workmanship and it will repair or replace any
product or part thereof which proves to be defective in workmanship or materials during the life expectancy of the product. This period is
determined to be no longer than 10 years starting from the date of manufacture. Please visit Global Fire Equipment’s web site
(www.globalfire.pt) for a full description of Global Fire Equipment’s LIMITED WARRANTY, which, among other things, limits the duration of
warranties of merchantability and fitness for a particular purpose and excludes liability for consequential damages. Acceptance of order
and/ or original invoice which will become part of your sales agreement. Please contact Global Fire Equipment’s web site for details on how
to obtain a return Merchandise Authorization Number (RMA) before returning goods to the factory. Shipment must be prepaid and Global
Fire Equipment will repair or replace your returned detector.
LIFETIME WARRANTY
To lock detector remove pin available at
terminal 4 on the underside of the
sounder using a small screwdriver.
To unlock detector from its base push
unlock key provided through hole
available on the base side wall as shown.
DETECTOR BASE LOCK
Detector Head
Detector Base
Alignment Marks
MECHANICAL SPECIFICATION
ORDER CODE
Loop Powered - 17 V to 30 V DC
450 uA max.
4 mA - Alarm LED Iluminated
According to EN54-5 and EN54-7
0.5-2.5 mm²
20 seconds max.
White / ABS
-10ºC to 50ºC / 95% RH Non-Condensing
100 mm (D) x 50 mm (H) inc. base / 144 g inc. base
TECHNICAL SPECIFICATIONS
SUPPLY VOLTAGE
CURRENT - QUIESCENT / SURGE
CURRENT - DEVICE IN ALARM
SENSITIVITY
CABLE SIZE
RESET/STAR-UP TIMES
COLOUR / CASE MATERIAL
OPER. TEMPERATURE / MAX. HUMIDITY
DIMENSIONS / WEIGHT
DESCRIPTION
Analogue Addressable Smoke Detector w/ Isolator and SAM
Analogue Addessable Heat Detector w/ Isolator and SAM
Analogue Addr. Combined Smoke & Heat Detector w/ Isolator and SAM
ZEOS-AS-SI
ZEOS-AS-HI
ZEOS-AS-SHI
GLOBAL FIRE EQUIPMENT S.A.
Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL
Tel: +351 289 896 560 • Sales: sales@globalfire.pt • Technical Support: techs@globalfire.pt • www.globalfire.pt
Made in Portugal-EU
Question and Answer IconNeed help?

Do you have a question about the Global Fire ZEOS AS series and is the answer not in the manual?

Global Fire ZEOS AS series Specifications

General IconGeneral
BrandGlobal Fire
ModelZEOS AS series
CategorySecurity Sensors
LanguageEnglish

Summary

Detector Base Lock Mechanism

Mechanical and Technical Specifications

Lifetime Product Warranty

Key Product Features

Dual LED Indicators

Provides 360-degree visibility for status indication.

Advanced Communication

Utilizes advanced protocols for detection and communication.

Installation and Maintenance

Designed for straightforward installation and upkeep.

Low-Profile Housing

Features a discreet and modern low-profile design.

Durable Sensor Head

Equipped with a robust sensor head that does not require replacement.

SMD Circuit Board Design

Incorporates SMD technology for high quality and reliability.

Installation Procedures

Installing the Base

Ensures proper fit of the detector head to the base via wire dressing.

Installing the Head

Aligns detector components and twists clockwise to secure.

Detector Testing

Details testing procedures for smoke and heat detection.

Maintenance Requirements

Recommends annual cleaning of dust from the detector head.

Address Programming

Smart Addressing Mechanism (SAM)

Explains SAM for address setting via programmer or ASET mode.

Compatibility Requirements

Lists compatible panels and software versions for SAM.

Pre-Programming Checks

Lists essential checks before starting the programming procedure.

Programming Caution

Warns about polarity reversal and system faults during programming.

Related product manuals