EasyManuals Logo

Globe GL Series User Manual

Globe GL Series
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
APR 2017 GFS-520a (Formerly A-58)
EXTENDED
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES DRY TYPE
HORIZONTAL SIDEWALL
DESCRIPTION AND OPERATION
RECESSED
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
Water Working Pressure Rating - 175 psi (12 Bars)
Factory tested hydrostatically to 500 psi (34 Bars)
Maximum low temperature glass bulb rating is -67°F (-55°C)
Frame - bronze De ector - brass Screw - brass
Bulb Seat - brass Spring - nickel alloy Seal - te on
Retainer - brass Pin - stainless steel
Torsion Spring - stainless steel Ori ce Insert - brass
Bulb - glass with alcohol based solution, 3mm size
3/4”NPT or 1”NPT Outer Tube - galvanized steel pipe
Inner Tube - stainless steel
TECHNICAL DATA
See reverse side for Approvals and Speci cations.
Temperature Ratings -
135°F (57°C), 155°F (68°C), 175°F (79°C)
200°F (93°C), 286°F (141°C)
SLEEVE & SKIRT
SURFACE MOUNT
CLASSIFICATION
AVAILABLE SPRINKLER
TEMPERATURES
BULB COLOR
N.F.P.A. MAXIMUM CEILING
TEMPERATURE
ORDINARY
INTERMEDIATE
HIGH
135°F/155°F
175°F/200°F
286°F
57°C/68°C
79°C/93°C
141°C
ORANGE/RED
YELLOW/GREEN
BLUE
100°F
150°F
225°F
38°C
66°C
107°C
The Globe Quick Response GL Series Dry Type Horizontal Sidewall
Sprinkler is designed for use in special applications such as freezing
environments and conditions where sediment or foreign materials might
accumulate in ordinary horizontal pipe nipples.
The Globe Quick Response GL Series Dry Type Horizontal Sidewall
Sprinkler utilizes a 3mm frangible glass ampule as the thermosensitive
element. This provides sprinkler operation approximately six times
faster than ordinary sprinklers. At the ampule's rated temperature,
the sprinkler opens releasing the bulb seat, causing the inner tube
assembly to move, allowing the spring assembly to pivot alongside
the inner tube. At this time, water ows through the sprinkler and is
distributed by the de ector, in an approved discharge pattern. It can be
installed wherever standard spray sprinklers are speci ed but offers the
additional feature of greatly increased safety to life. Quick Response
Sprinklers should be used advisedly and under the direction of approv-
ing authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating assembly
is a hermetically sealed frangible glass ampule that contains a precisely
measured amount of uid. When heat is absorbed, the liquid within
the bulb expands increasing the internal pressure. At the prescribed
temperature the internal pressure within the ampule exceeds the
strength of the glass causing the glass to shatter. This results in water
discharge which is distributed in an approved pattern.

Other manuals for Globe GL Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Globe GL Series and is the answer not in the manual?

Globe GL Series Specifications

General IconGeneral
BrandGlobe
ModelGL Series
CategoryIrrigation System
LanguageEnglish