SUCTION PRESSURE
SATURATED SUCTION
TEMPERATURE ºF
PSIG R-22
50 26
52 28
54 29
56 31
58 32
60 34
62 35
64 37
66 38
68 40
70 41
72 42
74 44
76 45
78 46
80 48
85 50
90 53
95 56
100 59
110 64
120 69
130 73
140 78
150 83
160 86
170 90
SATURATED SUCTION PRESSURE
TEMPERATURE CHART
LIQUID PRESSURE
SATURATED LIQUID
TEMPERATURE ºF
PSIG R-22
200 101
210 105
220 108
225 110
235 113
245 116
255 119
265 121
275 124
285 127
295 130
305 133
325 137
355 144
375 148
405 155
415 157
425 n/a
435 n/a
445 n/a
475 n/a
500 n/a
525 n/a
550 n/a
575 n/a
600 n/a
625 n/a
SATURATED LIQUID PRESSURE
TEMPERATURE CHART
55 57 59 61 63 65 67 69 71
60
10 13 17 20 23 26 29 30 31
65
8 1114161922262729
70
5 8 10 13 15 19 23 24 25
75
--------6 9 1115202123
80
---- ---- ---- ---- 7 12 17 18 20
85
---- ---- ---- ---- ---- 8 13 15 16
90
---- ---- ---- ---- ---- 5 10 11 13
95
---- ---- ---- ---- ---- ---- 5 8 10
100
---------------------------- 5 8
105
-------------------------------- 5
110
------------------------------------
115
------------------------------------
Indoor Wet Bulb Temperature, °F
Outdoor
Dry Bulb
Temperature, °F
SYSTEM SUPERHEAT