CONDENSING AC UNIT
SINGLE / THREE PHASE AIR CONDITIONERS
INSTALLATION & SERVICE REFERENCE
© 2010-2011 Goodman Manufacturing Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com -or- www.amana-hac.com
P/N: IO-402E Date: December 2011
Fixed Orifice
CAUTION
To prevent personal injury, carefully connect and disconnect
manifold gauge hoses. Escaping liquid refrigerant can cause
burns. Do not vent refrigerant into the atmosphere. Recover all
refrigerant during system repair and before final unit disposal.
1. Purge gauge lines. Connect service gauge manifold to
base-valve service ports. Run system at least 10 min-
utes to allow pressure to stabilize.
2. Temporarily install thermometer on suction (large) line
near suction line service valve with adequate contact and
insulate for best possible reading.
3. Refer to the superheat table provided for proper system
superheat. Add charge to lower superheat or recover
charge to raise superheat.
4. Disconnect manifold set, installation is complete.
Superheat Formula = Suct. Line Temp. - Sat. Suct. Temp.
Important Safety Instructions
The following symbols and labels are used throughout this
manual to indicate immediate or potential safety hazards. It
is the owner’s and installer’s responsibility to read and com-
ply with all safety information and instructions accompanying
these symbols. Failure to heed safety information increases
the risk of personal injury, property damage, and/or product
damage.
HIGH VOLTAGE!
Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
NOTICE
THIS UNIT IS SHIPPED WITH A NITROGEN/HELIUM
HOLDING CHARGE ONLY. UNIT MUST BE EVACUATED
AND CHARGED PER INSTALLATION INSTRUCTIONS
WITH REFRIGERANT LISTED ON SERIAL RATING PLATE.
NOTICE
UNITS SHIPPED WITH A HOLDING CHARGE ARE
INTENDED FOR COMPONENT REPLACEMENT ONLY ON
EXISTING SYSTEMS, AND NOT INTENDED FOR USE IN
NEW SYSTEMS OR NEWLY CONSTRUCTED HOMES.
NOTICE
UNITS MUST ONLY BE USED AS REPLACEMENT
COMPONENTS FOR PRE-2010 INSTALLED SYSTEMS.
55 57 59 61 63 65 67 69 71
60 10 13 17 20 23 26 29 30 31
65 8 1114161922262729
70 5 8 10 13 15 19 23 24 25
75 ---- ---- 6 9 11 15 20 21 23
80 ---- ---- ---- ---- 7 12 17 18 20
85
---- ---- ---- ---- ---- 8 13 15 16
90 ---- ---- ---- ---- ---- 5 10 11 13
95
---- ---- ---- ---- ---- ---- 5 8 10
100 ---- ---- ---- ---- ---- ---- ---- 5 8
105
---- ---- ---- ---- ---- ---- ---- ---- 5
110 ---- ---- ---- ---- ---- ---- ---- ---- ----
115 ---- ---- ---- ---- ---- ---- ---- ---- ----
Indoor Wet Bulb Temperature, °F
Outdoor
Dry Bulb
Temperature, °F
SYSTEM SUPERHEAT
Approximate charge shown for 15’ of 3/8” liquid line. System charge must be
adjusted per final charge adjustment (Page 7.)
Models
Nominal
Charge
(oz.)
GSC13018 75
GSC13024 77
GSC13030 66
GSC13036 77
GSC13042 95
GSC13048 89
GSC13060 131

Questions and Answers

  • P
    Peter ArnoldSep 23, 2025
    What to do if Goodman GSC13018 has too much air across indoor coil?
    • C
      Charles DuranSep 23, 2025
      If there is too much air across the indoor coil of your Goodman Air Conditioner, reduce the blower speed.
  • S
    sparkstammyAug 23, 2025
    What to do if Goodman Air Conditioner has overcharge of refrigerant?
    • D
      Dr. Elijah LeonAug 23, 2025
      If you have an overcharge of refrigerant in your Goodman Air Conditioner, recover part of the charge.
  • K
    Kim HernandezAug 25, 2025
    How to fix loose connection in Goodman Air Conditioner?
    • J
      Jacob ByrdAug 26, 2025
      If your Goodman Air Conditioner has a loose connection, inspect the connection and tighten it.
  • C
    Carlos PhillipsAug 27, 2025
    How to test shorted or broken wires in Goodman GSC13018?
    • P
      powellstaceyAug 27, 2025
      If your Goodman Air Conditioner has shorted or broken wires, test the circuits with an ohmmeter.
  • S
    sbrownAug 27, 2025
    What to do if Goodman GSC13018 Air Conditioner has noncondensibles?
    • C
      Christina JonesAug 28, 2025
      If your Goodman Air Conditioner has noncondensibles, recover the charge, evacuate, and recharge.
  • M
    Matthew PittmanSep 18, 2025
    What to do if Goodman Air Conditioner has not enough air across indoor coil?
    • M
      Melissa TorresSep 18, 2025
      If there is not enough air across the indoor coil of your Goodman Air Conditioner, increase the blower speed and check the duct static pressure.
  • A
    Ashley HamiltonSep 15, 2025
    What to do if Goodman GSC13018 Air Conditioner has undersized liquid line?
    • J
      Jesse GarciaSep 15, 2025
      If the liquid line is undersized in your Goodman Air Conditioner, replace the line.
  • S
    Shannon ZimmermanSep 16, 2025
    What to do if Goodman GSC13018 has undersized suction line?
    • M
      Morgan HarveySep 16, 2025
      If the suction line is undersized in your Goodman Air Conditioner, replace the line.
  • S
    Scott EvansSep 6, 2025
    How to test faulty fan relay in Goodman Air Conditioner?
    • J
      Jose BallardSep 6, 2025
      If your Goodman Air Conditioner has a faulty fan relay, test the continuity of the coil and contacts.
  • S
    Sharon OwensSep 3, 2025
    How to test shorted or grounded compressor in Goodman GSC13018?
    • L
      Lisa WashingtonSep 3, 2025
      If your Goodman Air Conditioner compressor is shorted or grounded, test the motor windings.

Summary

General Safety Warnings

High Voltage Warning

Disconnect all power before servicing to prevent property damage, personal injury or death.

Refrigerant Safety and Handling

Refrigerant Handling Precautions

Refrigerants are heavier than air; avoid breathing them. Wear gloves and goggles.

System Evacuation and Electrical Connections

Electrical Connection Safety

Disconnect power. Use copper conductors and follow NEC/CEC codes.

Charging and Final Adjustment

Troubleshooting Information

Troubleshooting Guide

Table lists common complaints, possible causes, symptoms, and test methods/remedies.