1.2 Exception Analyzing and Troubleshooting 
1.2.1 “d1” Indoor circuit board error 
Error display: 
IDU wired controller and IDU receive light board will display
 
Error judgment condition and method: 
Check if the reading of address chip and memory chip of IDU mainboard is normal. If the data of 
address chip and memory chip cannot be read, it is abnormal 
Possible reason:   
■Address chip is abnormal 
■Memory chip is abnormal. Replace main control board directly 
Troubleshooting: 
Replace main control board directly 
1.2.2 “d3” Ambient temperature sensor error 
Error display: 
IDU wired controller and IDU receive light board will display 
 
Error judgment condition and method: 
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge 
the  range  of  AD  value, If  the  sampling AD  value  exceeds  upper limit  and  lower limit  in  5  seconds 
continuously, report the error