GMV5 Compact Series VRF Outdoor Unit
16
thermal insulating material and adhesive pipe for insulation from the air;
2) For heat pump unit, liquid pipe should bear 70 or above, and gas pipe should bear 120 or above. For
cooling only unit, both liquid pipe and gas pipe should bear 70 or above.
Example: Polyethylene foam can bear 120 or above, and foaming polyethylene foam can bear 1200 or
above.
3) Joints at indoor and outdoor units should be wrapped with insulating material and leave no clearance
between pipe and wall. See Fig.13.
Fig.13
4) The foam attached on the manifold cannot be taken as insulating material.
5) When wrapping the tape, the later circle should cover half of the former one. Don’t wrap the tape so tightly,
otherwise the insulation effect will be weakened;
6) After wrapping the pipe, adopt sealing material to completely fill the hole so as to prevent wind and rain
from entering the room.
4.4.4 Support and Protection for Pipeline
(1) Support should be made for hanging connection pipe. Distance between each support cannot be over 1m;
(2) Protection towards accidental damage should be made for outdoor pipeline. When the pipeline exceeds 1m, a
pinch board should be added for protection.
No clearance
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.