GMV Heat Recovery DC Inverter VRF
16
Status
A+B+C+D
A+B
Status 4
a≥300
b≥100
c≥100
d≥100
e≥200
f≥500
Status 5
a≥300
b≥500
c≥100
d≥500
e≥200
f≥900
NOTES:
(1) The installation space shown above is based on the cooling operation when the outdoor
temperature is 35
. If the outdoor temperature exceeds 35
or the heat load is large, and
all outdoor units are operating at an excess capacity, the space at the suction side should be
increased.
(2) When disassembling or installing the unit, the operation may be affected by obstacles, and
the distance from the unit to the wall surface may be appropriately increased.
(3) When two or more units are installed and placed, the operation may be affected by the
adjacent units. The distance between the two adjacent units is “e” ≥ 100mm.
Unit: mm
Fig.3.2.7
(4) If the unit is installed in the space with four walls, wall height at both side of the unit shall
have no limit; wall height at return air side is below 500mm and at the front side is below
1,500mm. The unit is installed in a space with only two walls, A and B, and the height of the
B wall is not limited.
(5) If the wall exceeds the above value, increase the space as follows.