GMV Heat Recovery DC Inverter VRF
28
10
Piping between indoor branches (“l”)
Rated capacity of the
downstream indoor units
C(kW)
Size of connection pipe between indoor branches
Gas pipe (mm) Liquid pipe (mm)
C2.8 Φ9.52 Φ6.35
2.8<C5.0 Φ12.7 Φ6.35
5.0<C14.2 Φ15.9 Φ9.52
14.2<C≤16 Φ19.05 Φ9.52
3.3.6 Connecting method for indoor unit with capacity of over 16kW
When connecting to the indoor unit with capacity of over 16kW, it is not allowed to connect with
only one branch; it must use two branches controlled by the same mainboard for parallel connection.
Parallel
connection
Dial code
Indoor unit
communication
connection for mode
exchange box
Remarks
Indoor unit No.1
and No.2
1D1 1D2 or 2D1
2D2
Parallel connection can be
conducted only as the
combination of this table; it is
not allowed to otherwise
connect. Note that after the
connection, manually set the
SA1 dial code of corresponding
mainboard, and dial the code
as shown in the table.
Indoor unit No.2
and No.3
2D1 2D2 or 3D1
3D2
Indoor unit No.3
and No.4
3D1 3D2 or 4D1
4D2
Indoor unit No.1
and No.2
Indoor unit No.3
and No.4
1D1 1D2 or 2D1
2D2 and
3D1 3D2 or 4D1
4D2
Connecting method is as shown in the picture: