EasyManua.ls Logo

Gree GMVVQ224WM/C-X - Page 47

Gree GMVVQ224WM/C-X
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GMV Heat Recovery DC Inverter VRF
43
Model
Combination
method
Power spec
Capacity of circuit
breaker of each
combination
module (A)
Minimum cross-
sectional area of
grounding wire
(mm
2
)
Recommended wire
(cross-sectional area)
(mm
2
)
GMV-
VQ450WM/C-
X
380-415V
3N
50/60Hz
40 6.0
6.0
×
5
GMV-
VQ504WM/C-
X
380-415V
3N
50/60Hz
50 10.0
10.0
×
5
GMV-
VQ560WM/C-
X
380-415V
3N
50/60Hz
50 10.0
10.0
×
5
GMV-
VQ615WM/C-
X
380-415V
3N
50/60Hz
50 10.0
10.0
×
5
GMV-
VQ680WM/C-
X
280+400
380-415V
3N
50/60Hz
25+40 2.5+6.0
2.5
×
5+6.0
×
5
GMV-
VQ730WM/C-
X
280+450
380-415V
3N
50/60Hz
25+40 2.5+6.0
2.5
×
5+6.0
×
5
GMV-
VQ784WM/C-
X
280+504
380-415V
3N
50/60Hz
25+50 2.5+10.0
2.5
×
5+10.0
×
5
GMV-
VQ840WM/C-
X
280+560
380-415V
3N
50/60Hz
25+50 2.5+10.0
2.5
×
5+10.0
×
5
GMV-
VQ895WM/C-
X
280+615
380-415V
3N
50/60Hz
25+50 2.5+10.0
2.5
×
5+10.0
×
5
GMV-
VQ950WM/C-
X
335+615
380-415V
3N
50/60Hz
25+50 4.0+10.0
4.0
×
5+10.0
×
5
GMV-
VQ1015WM/C-
X
400+615
380-415V
3N
50/60Hz
40+50 6.0+10.0
6.0
×
5+10.0
×
5
GMV-
VQ1065WM/C-
X
450+615
380-415V
3N
50/60Hz
40+50 6.0+10.0
6.0
×
5+10.0
×
5
GMV-
VQ1119W M/C-
X
504+615
380-415V
3N
50/60Hz
50+50 10.0+10.0
10.0
×
5+10.0
×
5
GMV-
VQ1175WM/C-
X
560+615
380-415V
3N
50/60Hz
50+50 10.0+10.0
10.0
×
5+10.0
×
5
GMV-
VQ1230WM/C-
X
615+615
380-415V
3N
50/60Hz
50+50 10.0+10.0
10.0
×
5+10.0
×
5
GMV-
VQ1290WM/C-
X
280+450+560
380-415V
3N
50/60Hz
25+40+50 2.5+6.0+10.0
2.5
×
5+6.0
×
5+10.0
×
5
GMV-
VQ1345WM/C-
X
280+450+615
380-415V
3N
50/60Hz
25+40+50 2.5+6.0+10.0
2.5
×
5+6.0
×
5+10.0
×
5
GMV-
VQ1400WM/C-
X
335+450+615
380-415V
3N
50/60Hz
25+40+50 4.0+6.0+10.0
4.0
×
5+6.0
×
5+10.0
×
5
GMV-
VQ1455WM/C-
X
280+560+615
380-415V
3N
50/60Hz
25+50+50 2.5+10.0+10.0
2.5
×
5+10.0
×
5+10.0
×
5

Related product manuals