GMV Heat Recovery DC Inverter VRF
61
the next step of detection.
—
Meaning
Progress
Code
Display
Code
Display
Code
Display
05_ detect
internal
communication
db ON 05 ON OC ON
Once the system
inspection is completed,
it will enter into the next
If an abnormality is detected, it will stay in the current state and manual troubleshooting is required.
The corresponding faults are as below:
—
Meaning
Progress
Code
Display
Code
Display
Code
Display
05_ detect internal
communication
db ON 05 ON C1 ON
The system has detected
“
Communication
control and DC-DC
”
db ON 05 ON C2 ON
The system has detected
“
communication
control and inverter
”
db ON 05 ON C3 ON
The system has detected
“
communication
control and inverter fan
”
db ON 05 ON CH ON
Indoor/outdoor units’
rated
capacity ratio is too high.
db ON 05 ON CL ON
Indoor/outdoor units’
rated
capacity ratio is too low.
Refer to the part of “Troubleshooting” for the corresponding troubleshooting method.
Step 9: The unit debugging step 06 is “outdoor unit components inspection”.
If there is no abnormality in the detection, the display is below, and then it automatically enters
the next step of detection.
—
Meaning
Progress
Code
Display
Code
Display
Code
Display
06_outdoor unit
components
inspection
db ON 06 ON OC ON
The system detected that
there’
unit’s parts. Then it will
automatically enter into
If an abnormality is detected, it will stay in the current state and manual troubleshooting is required.
The corresponding faults are as below.