GMV Heat Recovery DC Inverter VRF
64
If inspection valve of the unit is normal, the display is as below. The unit will automatically enter
into the next step.
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
10_ status judgment of
main pipeline before
starting
db ON 10 ON OC ON
The main pipeline is turned on
normally
Step 14: Unit debugging step 11 is “reserved function”.
The main module display is as below. The unit automatically enters into the next step.
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
11_ reserved function
db
ON
11
ON
AE
ON
Step 15: Unit debugging step 12 is “reserved function”.
The master module display is as below. Then the unit automatically enters into the next step.
Debugging code Progress code Status code
Meaning
Progress
LED1 LED2 LED3
Code
Display
status
Code
Display
status
Code
Display
status
12_reserved function db ON 12 ON 01 ON
Step 16: After the unit debugging method is confirmed, the system automatically selects cooling
or heating mode according to the ambient temperature.
Once cooling/heating mode is selected, the relevant display is as below.
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
13~15_pilot run
stage
db ON
13/14/
15
ON AC ON Pilot run of cooling mode
db ON
13/14/
15
ON AH ON Pilot run of heating mode
db ON
13/14/
15
ON
Correspo
nding
error
code
ON
Theres fault on pilot run stage.
Note: fault module display
db ON
13/14/
15
ON J0 ON
Theres fault on pilot run stage.
Note: non-fault module display
db ON
13/14/
15
ON U9 ON
Outdoor units pipeline or valve is
abnormal.
db ON
13/14/
15
ON XXXX/U8
ON
The system detected the indoor
units pipeline is abnormal. XXXX
indicates engineering number of
fault indoor unit. 2s later, U8 fault
occurred for No. 100 indoor unit.
LED3 will display as below: 01 (2s
later) 00 (2s later) U8, and it will
display like that circularly.
Note: In the pilot run stage, the unit will display corresponding procedures according to actual
circumstances.