23
Installation and Maintenance
that the work is carried out. The ventilation should safely disperse 
any released refrigerant and preferably expel it externally into the 
atmosphere.
●Checks to the refrigeration equipment
Where electrical components are being changed, they shall be 
fit for the purpose and to the correct specification. At all times 
the manufacturer’s maintenance and service guidelines shall 
be followed. If in doubt, consult the manufacturer’s technical 
department for assistance.
The following checks shall be applied to installations using 
ammable refrigerants:
---The actual refrigerant charge is in accordance with the room size 
within which the refrigerant containing parts are installed;
---The ventilation machinery and outlets are operating adequately 
and are not obstructed;
---If an indirect refrigerating circuit is being used, the secondary 
circuit shall be checked for the presence of refrigerant;
---Marking to the equipment continues to be visible and legible. 
Markings and signs that are illegible shall be corrected;
---Refrigeration pipe or components are installed in a position 
where they are unlikely to be exposed to any substance which may 
corrode refrigerant containing components, unless the components 
are constructed of materials which are inherently resistant to being 
corroded or are suitably protected against being so corroded.
●Checks to electrical devices
Repair and maintenance to electrical components shall include 
initial safety checks and component inspection procedures. If a 
fault exists that could compromise safety, then no electrical supply 
shall be connected to the circuit until it is satisfactorily dealt with. 
If the fault cannot be corrected immediately but it is necessary to 
continue operation, an adequate temporary solution shall be used. 
This shall be reported to the owner of the equipment so all parties 
are advised.
Initial safety checks shall include:
1.That capacitors are discharged: this shall be done in a safe 
manner to avoid possibility of sparking;
2.That no live electrical components and wiring are exposed while 
charging, recovering or purging the system;
3.That there is continuity of earth bonding.
●Repairs to sealed components
1. During repairs to sealed components, all electrical supplies shall 
be disconnected from the equipment being worked upon prior to 
any removal of sealed covers, etc. If it is absolutely necessary to 
have an electrical supply to equipment during servicing, then a 
permanently operating form of leak detection shall be located at 
the most critical point to warn of a potentially hazardous situation.
2. Particular attention shall be paid to the following to ensure that 
by working on electrical components, the casing is not altered in 
such a way that the level of protection is aected.This shall include 
damage to cables, excessive number of connections, terminals not 
made to original specication, damage to seals, incorrect tting of 
glands, etc.
Ensure that the apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded to the 
point that they no longer serve the purpose of preventing the 
ingress of flammable atmospheres.
Replacement parts shall be in accordance with the manufacturer’s 
specications.
NOTE : The use of silicon sealant can inhibit the effectiveness of some 
types of leak detection equipment. Intrinsically safe components do not 
have to be isolated prior to working on them.
●Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the 
circuit without ensuring that this will not exceed the permissible 
voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be 
worked on while live in the presence of a flammable atmosphere. 
The test apparatus shall be at the correct rating.
Replace components only with parts specified by the 
manufacturer. Other parts may result in the ignition of refrigerant 
in the atmosphere from a leak.
●Cabling
Check that cabling will not be subject to wear, corrosion, 
excessive pressure, vibration, sharp edges or any other adverse 
environmental effects. The check shall also take into account 
the effects of aging or continual vibration from sources such as 
compressors or fans.
●Detection of ammable refrigerants
Under no circumstances shall potential sources of ignition be used 
in the searching for or detection of refrigerant leaks. A halide torch 
(or any other detector using a naked flame) shall not be used.
●Leak detection methods
The following leak detection methods are deemed acceptable for 
all refrigerant systems.
Electronic leak detectors may be used to detect refrigerant leaks 
but, in the case of flammable refrigerants, the sensitivity may not 
be adequate, or may need re-calibration.
(Detection equipment shall be calibrated in a refrigerant-free 
area.) Ensure that the detector is not a potential source of ignition 
and is suitable for the refrigerant used.
Leak detection equipment shall be set at a percentage of the 
LFL of the refrigerant and shall be calibrated to the refrigerant 
employed, and the appropriate percentage of gas (25 % 
maximum) is conrmed.
Leak detection fluids are suitable for use with most refrigerants 
but the use of detergents containing chlorine shall be avoided as 
the chlorine may react with the refrigerant and corrode the copper 
pipe-work.
If a leak is suspected, all naked flames shall be removed/
extinguished.
If a leakage of refrigerant is found which requires brazing, all of 
the refrigerant shall be recovered from the system, or isolated (by 
means of shut o valves) in a part of the system remote from the 
leak. For appliances containing flammable refrigerants, oxygen 
free nitrogen (OFN) shall then be purged through the system both 
before and during the brazing process
.
●Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or 
for any other purpose –conventional procedures shall be used. 
However, for flammable refrigerants it is important that best 
practice is followed since flammability is a consideration. The 
following procedure shall be adhered to:
1.remove refrigerant;
2.purge the circuit with inert gas; evacuate;
3.purge again with inert gas;
4.open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery 
cylinders.
For appliances containing flammable refrigerants, the system 
shall be “flushed” with OFN to render the unit safe. This process 
may need to be repeated several times.Compressed air or oxygen