Compressor’s starting interval should be more than 3 minutes no matter in whatever modes
and conditions. If it’s plugged in first time, the compressor does not have 3 minutes delay. When
compressor is started, it will not stop within 5 minutes unless it is plugged out.
c. overload protection
If it detect the system current surpass the designed 13 A for continuous 3 minutes, the machine
go into fan mode, when 3 minutes passed and it detect the current no more than 13 A, it will back
to original state. If it detects overloading states for 3 consecutive times within 30 minutes, the
machine stops, and must be restarted by remote controller.
d. locked motor protection
if it detects no feedback from the PG motor for continuous 15 seconds , the machine stops,
after 3 minutes delay, the machine backs to original state. If the motor be detected locked for 3
consecutive times, the whole machine stops and can not run again automatically.
2.dehumidifying mode
(1) the working conditions and control measures
a. if T
in
T
set
+2 , it is in cooling running, the indoor motor speed can be selected ,and outdoor
motor run at low speed.
b. If T
set
-2 T
in
T
set
+2 ,it goes into dehumidifying running ,the indoor motor run at the low
speed, 6 minutes later the compressor stops, another 15 seconds later the outdoor fan stops
and another 30 seconds later, the indoor motor stops, 3 and a half minutes later, compressor
and outdoor fan run again ,indoor motor runs at the low speed, then the machine cycle the
above procedures repeatedly. outdoor motor runs at the low speed.
c. If T
in
T
set
-2 , compressor ,outdoor motor and indoor motor stop.
(2) in this mode, the reversing valve is inactive , the temp. setting range is 16~30
.
(3) Anti-freezing protection.
If T
indoor
T
set
+ 2
, it goes into cooling running , anti-freezing function is same with cooling
mode, but the compressor must stops for 4 minutes. when it goes into dehumidifying mode, com-
pressor runs 6 minutes , if it detects T
eva
0 ,compressor and outdoor motor stop, indoor motor
runs at low speed ,after 3 minutes delay ,and T
eva
10 ,it will be back to its original state.
(4) Overload is same as the one in cooling mode.
3.heating mode
(1)the working conditions and control measures
a. If T
in
T
set
+2 , it goes into heating mode, reversing valve, compressor and outdoor motor
all work in the same time, indoor fan will run at the same procedures with anti cool air function.
b. If T
in
T
set
+ 4
, compressor stops first, 15 seconds late, outdoor motor stops ,but reversing
valve keeps working, indoor motor run at the procedures of blowing surplus heat.
d. if T
set
+ 2 < T
indoor
< T
set
+4 , keep the previous running state.
e. If T
outdoor
3 , outdoor runs at high speed, if T
outdoor
5 ,outdoor motor runs at low speed
.if 3
T
outdoor
5 ,keep the previous running state.
(2)in this mode, the temperature setting range is from 16~30
.