U-Match Series DC Inverter Service Manual
33
4.9.8 Selecting door control function
Under debugging state, press Mode button to adjust to “08” in temperature displaying zone. Timer
zone displays setting state and press ▲ or ▼ button to adjust. There are 2 selections:
(1) Without door control function (LCD displays 00)
(2) With door control function (LCD displays 01)
4.9.9 Selecting human sensitive function
Under debugging state, press Mode button to adjust to “09” in temperature displaying zone. Timer
zone displays setting state and press ▲ or ▼ button to adjust. There are 2 selections:
(1) Without human sensitive function (LCD displays 00)
(2) With human sensitive function (LCD displays 00)
4.9.10 Selecting long-distance monitoring or centralized controller
Under debugging state, press Mode button to adjust to “10” in temperature displaying zone. Timer
zone displays setting state and press ▲ or ▼ button to adjust. There are 2 selections:
(1) Centralized controller (LCD displays 00)
(2) Long-distance monitoring (LCD displays 01)
4.9.11 Selecting fan mode of indoor fan motor
Under debugging state, press Mode button to adjust to “11” in temperature displaying zone. Timer
zone displays setting state and press ▲ or ▼ button to adjust. There are 5selections:
(1) P3 (LCD displays 03)
(2) P4 (LCD displays 04)
(3) P5 (LCD displays 05)
(4) P6 (LCD displays 06)
(5) P7 (LCD displays 07)
Note:
You can select P03, P04, P05, P06, P07 in fan mode of indoor fan motor, which means
different fan mode combinations are corresponding to different static pressure. Ex-factory defaulted
mode is P05. You can set the mode through wired controller. S01, S02, S03……S12, S13 means the
rotation speed of indoor unit is from low to high.
Table 2-4-2 Combination relationship of P03, P04, P05, P06, P07
Static
pressure
selection
Super
high
speed
High
speed
Medium
high
speed
Medium
speed
Medium
low
speed
Low
speed
Quiet
R1
speed
Quiet
R2
speed
Quiet
R13
speed
P03
S09
S08
S07
S06
S05
S04
S03
S02
S01
P04
S10
S09
S08
S07
S06
S05
S04
S03
S02
P05
S11
S10
S09
S08
S07
S06
S05
S04
S03
P06
S12
S11
S10
S09
S08
S07
S06
S05
S04
P07
S13
S12
S11
S10
S09
S08
S07
S06
S05
4.9.12 Selecting compensation of temperature sensor at air return
Under debugging state, press Mode button to adjust to “12” in temperature displaying zone. Timer
zone displays setting state and press ▲ or ▼ button to adjust. There are 16 selections:
(1) Compensate 0 (LCD displays 00)
(2) Compensate 1 (LCD displays 01)
(3) Compensate 2 (LCD displays 02)