DC Inverter U-match Series Duct Type Unit
43
Model
Power supply
Circuit
breaker
capacity
Min. sectional
area of power
cord
V/Ph/Hz
A
mm
2
GUD35W/NhA-T
220-240V ~50Hz
208-230V ~60Hz
16
1.5
GUD50W/NhA-T
16
1.5
GUD71W/NhA-T
20
2.5
GUD85W/NhA-T
25
2.5
GUD100W/NhA-T
32
4.0
GUD125W/NhA-T
32
4.0
GUD140W/NhA-T
40
6.0
GUD100W/NhA-X
380-415V 3N~50/60Hz
16
1.5
GUD125W/NhA-X
16
1.5
GUD140W/NhA-X
16
1.5
GUD160W/NhA-X
16
1.5
NOTES:
. Fuse is located on the main board.
. Install a circuit breaker at every power terminal near the units (indoor and
outdoor units) with at least 3mm contact gap. The units must be able to be
plugged or unplugged.
. Circuit breaker and power cord specifications listed in the above table are
determined based on the maximum power input of the units.
. Specifications of power cords listed in the above table are applicable in a
working condition where ambient temperature is 40°C and multi-core copper
cable (e.g. YJV copper cable, with insulated PE and PVC sheath) is protected
by a conduit, and is resistant to 90°C in maximum (See IEC 60364-5-52). If
working condition changes, please adjust the specifications according to
national standards.
. Specifications of circuit breaker are based on a working condition where the
working temperature is 40°C. If working condition changes, please adjust the
specifications according to national standards.
. Adopt 2pc of 0.75mm² power cords to be the communication cords between
indoor and outdoor units. The maximum length is 100m. Please select a