GREE U-Match 5 SERIES UNIT SERVICE MANUAL
149
Removal of fan and motor
Note: Before removal, make sure power
is cut off. During the removal procedure, take good care of all the components, especially
the screws of fan.
Step Picture Work instruction
1. Remove the volutes.
Press the retaining ring at
the joint of front and rear
volutes. Then pull up the
front volute. Then loosen the
screws of the rear volute. Lift
up the retaining ring of the
rear volute and take it off.
(As shown in the picture, the
lines indicate the screws on
both sides of the volutes.
2. Remove the fan.
Loosen the 2 screws of the
coupler. Take out the shaft
and axial flow fan. Loosen
the screws of axial flow fan
and remove the axial flow
fan.
3. Remove the bearing fixed
plate.
Twist off the screws and nuts
of bracket. Then remove the
bracket.
4. Remove the motor
Loosen the 2 screws of the
motor securing clip. Remove
the motor securing clip and
its assembly.