DC Inverter U-match Series Floor Ceiling Type Unit
34
3.3.2 Electrical Parameters
3.3.2.1 Wire Specifications and Fuse Capacity
NOTICE:
① Fuse is located on the main board.
② Install a circuit breaker at every power terminal near the units (indoor and
outdoor units) with at least 3mm contact gap. The units must be able to
be plugged or unplugged.
③ Circuit breaker and power cord specifications listed in the above table are
determined based on the maximum power input of the units.
④ Specifications of power cords listed in the above table are applicable in a
working condition where ambient temperature is 40℃ and multi-core
copper cable (e.g. YJV copper cable, with insulated PE and PVC sheath)
is protected by a conduit, and is resistant to 90℃ in maximum (See IEC
60364-5-52). If working condition changes, please adjust the
specifications according to national standards.