DC Inverter U-match Series Duct Type Unit
8
1) Refrigerant charging quantity for the entire system (ex-factory
charging quantity + additional charging quantity).
2) Checking out in the applicable tables:
A. For indoor unit, confirm the model of indoor unit and check the
corresponding table.
B. For outdoor unit that is installed or placed indoors, select the
corresponding table according to the height of the room.
Height of the room
Select the applicable table
<1.8m
Floor standing type
P Wall mounted type
3) Refer to the following table to check out the minimum construction
area
Ceiling type Wall mounted type Floor standing type
Weight(kg)
Area (m
2
)
Weight(kg)
Area (m
2
)
Weight (kg)
Area (m
2
)
<
1.224
<
1.224
<
1.224
1.224 0.956 1.224 1.43 1.224 12.9
1.4 1.25 1.4 1.87 1.4 16.8
1.6 1.63 1.6 2.44 1.6 22.0
1.8 2.07 1.8 3.09 1.8 27.8
2.0 2.55 2.0 3.81 2.0 34.3
2.2 3.09 2.2 4.61 2.2 41.5
2.4 3.68 2.4 5.49 2.4 49.4
2.6 4.31 2.6 6.44 2.6 58.0
2.8
5.00
2.8
7.47
2.8
67.3
3.0 5.74 3.0 8.58 3.0 77.2
3.2 6.54 3.2 9.76 3.2 87.9
3.4 7.38 3.4 11.0 3.4 99.2
3.6 8.27 3.6 12.4 3.6 111
3.8 9.22 3.8 13.8 3.8 124
4.0 10.2 4.0 15.3 4.0 137
4.2 11.3 4.2 16.8 4.2 151
4.4 12.4 4.4 18.5 4.4 166
4.6 13.5 4.6 20.2 4.6 182
4.8 14.7 4.8 22.0 4.8 198