DC Inverter U-match Series Duct Type Unit
23
Item
Model
Size of Fitting
Pipe(inch)
Maximum
pipe
length(m)
Biggest drop between
indoor and outdoor
units(m)
Liquid pipe
Gas pipe
GUD71PH/B-S
GUD71PHS/B-S
Ɏ Ɏ
50 25
GUD100PH/B-S
GUD100PHS/B-S
65 30
GUD125PH/B-S
GUD125PHS/B-S
75 30
GUD140PH/B-S
GUD140PHS/B-S
75 30
GUD160PH/B-S
GUD160PHS/B-S
75 30
Connection pipe should adopt water-proof insulating material. Its wall thickness
should be 0.5-1.0mm and the pipe wall should be able to withstand 6.0MPa. The
longer the connection pipe is the worse cooling and heating performance it has.
When the drop between indoor and outdoor units is larger than 10m, an oil
return bend should be added every 6m.
The requirement on the adding of oil return bend is as below:
(1) Outdoor unit is beneath the indoor unit.
Theres no need to add non-return bend at the lowest or highest position of the
vertical pipe, as shown below: