DC Inverter U-match Series Duct Type Unit
28
communication wire during installation, use the sealing pad and rubber ring after
threading the connection pipe and power cord or communication wire to the
knock-down hole, and wrap the tail of sealing pad with the pipe when wrapping the
tape. Seal the knock-down hole well to prevent insects from entering to the unit. See
the following figures.
NOTICE: Only for the GUD100W/NhB-S, GUD125W/NhB-S,
GUD140W/NhB-S, GUD160W/NhB-S, GUD160W/NhB-X units.
3.2.4 Connection Pipe Vacuum Pumping and Leak Detection
3.2.4.1 Vacuum Pumping
NOTICE!
Make sure the outlet of vacuum pump is away from fire source and is
well-ventilated.
(1) Remove the caps of the liquid valve, gas valve and also the service port.
(2) Connect the hose at the low pressure side of the manifold valve assembly
to the service port of the unit’s gas valve, and meanwhile the gas and
liquid valves should be kept closed in case of refrigerant leak.
(3) Connect the hose used for evacuation to the vacuum pump.
(4) Open the switch at the lower pressure side of the manifold valve
assembly and start the vacuum pump. Meanwhile, the switch at the high
pressure side of the manifold valve assembly should be kept closed,
otherwise evacuation would fail.
(5) The evacuation duration depends on the unit’s capacity, generally.
Model Time(min)
20
GUD71PHS/B-S
GUD100PH/B-S
30