DC Inverter U-match Series Duct Type Unit
30
3.2.4.2 Leak Detection Methods
The following leak detection methods are deemed acceptable for systems
containing flammable refrigerants.
Electronic leak detectors shall be used to detect flammable refrigerants, but the
sensitivity may not be adequate, or may need re-calibration
(Detection equipment
shall be calibrated in a refrigerant-free area).
Ensure that the detector is not a potential source of ignition and is suitable for
the refrigerant used. Leak detection equipment shall be set at a percentage of the
LFL of the refrigerant and shall be calibrated to the refrigerant employed and the
appropriate percentage of gas (25% maximum) is confirmed.
Leak detection fluids are suitable for use with most refrigerants but the use of
detergents containing chlorine shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed / extinguished. If a
leakage of refrigerant is found which requires brazing, all of the refrigerant shall be
recovered from the system, or isolated (by means of shut off valves) in a part of the
system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged
through the system both before and during the brazing process.
3.2.5 Refrigerant Adding
NOTICE!
Before and during operation, use an appropriate refrigerant leak detector to
monitor the operation area and make sure the technicians can be well aware of
any potential or actual leakage of inflammable gas. Make sure the leak detecting
device is applicable to inflammable refrigerant. For example, it should be free of
sparks, completely sealed and safe in nature.
See the following table for the amount of additional refrigerant.
Item
Model
Performance
Te s ti ng Sta nd ard
Pipe Length(SL) ,
and refrigerant
charge amount
Factory
Pre-charge Pipe
length(PL),
pre-charge
refrigerant charge
amount
Refrigerant
charge
(g/m)adjustment
over or under
factory
pre-charge pipe
length
GUD50W/NhB-S
5m, 1100g
15m, 1300g
±20g/m
GUD71W/NhB-S
5m, 1600g
20m, 1970g
±25g/m