DC Inverter U-match Series Duct Type Unit 
 
 Item 
Model 
Size of Fitting 
Maximum 
pipe 
length(m) 
Biggest drop between 
indoor and outdoor 
units(m) 
Liquid pipe  Gas pipe 
GUD35P/A-T 
Ф1/4 
Ф3/8  30  15 
GUD50P/A-T 
Ф1/2  35  20 
GUD71P/A-T 
Ф3/8  Ф5/8 
50  25 
GUD71PH/A-T 
50  25 
GUD85P/A-T 
50  25 
GUD85PH/A-T 
50  25 
GUD100PH/A-T 
65  30 
GUD125PH/A-T 
75  30 
GUD140PH/A-T 
75  30 
GUD160PH/A-T 
75  30 
Connection pipe should adopt water-proof insulating material. Its wall thickness 
should be 0.5-1.0mm and the pipe wall should be able to withstand 6.0MPa. The 
longer the connection pipe is the worse cooling and heating performance it has.   
When the drop between  indoor and outdoor units is larger than 10m, an oil 
return bend should be added every 6 m.