DC Inverter U-match Series Floor Ceiling Type Unit
34
3.3.2 Electrical Parameters
3.3.2.1 Wire Specifications and Fuse Capacity
Model
Power supply
Fuse
capacity
Circuit
breaker
capacity
Min. sectional
area of power
cord
V/Ph/Hz
A
A
mm
2
Indoor
unit
220-240V 1N~50Hz
208-230V 1N~60Hz
3.15
6
1.0
Model
Power supply
Circuit
breaker
capacity
Min. sectional
area of power
cord
V/Ph/Hz
A
mm
2
GUD35W/NhA-T
220-240V 1N~50Hz
208-230V 1N~60Hz
16
1.5
GUD50W/NhA-T
16
1.5
GUD71W/NhA-T
20
2.5
GUD85W/NhA-T
25
2.5
GUD100W/NhA-T
32
4.0
GUD125W/NhA-T
32
4.0
GUD140W/NhA-T
40
6.0
GUD100W/NhA-X
380-415V 3N~50Hz/60Hz
16
1.5
GUD125W/NhA-X
16
1.5
GUD140W/NhA-X
16
1.5
GUD160W/NhA-X
16
1.5
NOTICE:
Fuse is located on the main board.
Install a circuit breaker at every power terminal near the units (indoor and
outdoor units) with at least 3mm contact gap. The units must be able to
be plugged or unplugged.
Circuit breaker and power cord specifications listed in the above table are
determined based on the maximum power input of the units.
Specifications of power cords listed in the above table are applicable in a
working condition where ambient temperature is 40 and multi-core
copper cable (e.g. YJV copper cable, with insulated PE and PVC sheath)
is protected by a conduit, and is resistant to 90 in maximum (See IEC
60364-5-52). If working condition changes, please adjust the
specifications according to national standards.