65
Installation and Maintenance
Service Manual
11.2 Removal Procedure of Outdoor Unit
Warning: Be sure to wait for a minimum of 20 minutes
after turning off all power supplies and discharge the
refrigerant completely before removal.
ProcedureSteps
1.Remove big handle
2. Remove top cover
Before disassamble.
Remove 3 connection screw fixing small
handle and then remove the big handle.
Remove 1 connection screw fixing valve cover
and then remove the valve cover.
Remove 3 connection screws among
top cover plate, front panel and right
side plate. Then remove top cover
plate.
screw
Small Handle
Valve Cover
screw
top cover plate