 14. Refrigerant Recovery Function (Applicable for Moving the Unit or Maintaining the Unit) 
(1) Start up refrigerant recovery function
Set cooling mode with remote controller within 5min after energization, adjust temperature at 16ºC and press light button on remote 
controller for 3 times successively to any one indoor unit within 3s and then the complete unit will enter into refrigerant recovery status. 
All indoor units display Fo. Maintenance person close all liquid valves. After 5min, withstand the thimble of all checking valves with 
tools one by one. If there’s no refrigerant spraying out, close corresponding valve immediately, turn off the unit with remote controller 
and then remove the connection pipe. 
(2) Exit refrigerant recovery function
During refrigerant recovery process,  if any  one indoor  unit  receives any remote control  signal or refrigerant  recovery function has 
operates for  about 25min, refrigerant recovery function will be exited automatically. If the complete unit is at  standby status  before 
refrigerant recovery, the complete unit will still at standby status after refrigerant recovery. If the complete unit is at ON status, the unit 
will operate according to original operation mode. 
(3) After  entering refrigerant  recovery function:  Indoor unit  operates  at  cooling  mode.  Fan  speed  is  super-high  speed  and set 
temperature is 16°C. Horizontal will open at the minimum operation angle.
15. Mode Shock 
When there’s indoor unit under operation, if start up other indoor unit and the setting mode is inconsistent with that indoor unit, mode 
shock will occur. The  indoor with mode shock  displays  “E7” and  indoor fan stops  operation.  Corresponding relationship for mode 
shock and operation status after shock is as below: 
Mode relationship table for mode shock
Mode Indoor unit with mode 
shock 
Operation status after mode shock
Indoor unit A
Indoor unit B
Indoor unit A Indoor unit B
Cooling/drying heating
Indoor unit B
Cooling/drying Indoor fan stops operation
Heating  Cooling, drying, fan  Indoor unit B Heating  Indoor fan stops operation
Fan  Heating  Indoor unit A Indoor fan stops operation Heating 
Note: (1) Indoor unit A: The indoor unit under operation currently 
          (2) Indoor unit B: The indoor unit is tuned on latter
          (3) If set auto mode with remote controller, the complete unit will judge according to actual operation mode under auto  mode.