29
Installation and Maintenance
Service Manual
(2) PG motor (indoor fan motor) does not operate (H6)
Stir the fan blade 
with a hand when 
the unit is DE -
ENERGIZED.
    Does the 
blade rotate 
unsmoothly?
Reinstall the motor 
and the blade to 
make it rotate 
smoothly.
Yes
          Is the 
        feedback 
terminal of PG 
   motor loose?
Insert the feedback 
terminal tightly .
Mainboard 
malfunction
; 
Replace it.
No
Yes
Replace the fan 
motor.
End
Insert the control 
terminal tightly.
Yes
No
                 Re-energize 
   to turn on the unit; 
measure within 1 min after the 
louvers are opened whether the output 
voltage on the control terminal  
  of the PG motor is over 50V?
No
Yes
No
   Is the 
malfunction 
eliminated? 
No
    Is the 
malfunction 
eliminated? 
No
No
No
Yes
Yes
Yes
Yes
       Is the 
control terminal 
of PG motor 
      loose?
    Is the 
malfunction 
eliminated? 
    Is the 
malfunction 
eliminated? 
     “H6”is 
displayed on 
    the unit.