1. Improper input voltage
2. Poor connection on reactor
3. Reactor damaged
4. Bad AP1 control board
Charging Malfunction of Capacitor
Status:
During cooling mode, compressor will stop,
indoor fan will run. Heating mode all units
stop.
PU
Error Code Diagnostics
H7 Error Code, continued on next page
Start Troubleshooting after unit
is powered on for 1 minute
Use a DC voltmeter to
measure the voltage
across the terminals of the
electrolytic capacitor
Yes
Replace AP1 circuit
board
Is the input AC voltage
between 201VAC & 250VAC?
No
Shut down power and wait 20
minutes or connect a DC voltmeter
to the electrolytic capacitor until the
voltage is less than 20 v
Voltage higher than 200v
Yes
End Troubleshooting
Yes
Correct input AC
power supply to unit
No
Restart the unit,
is the malfunction
corrected?
No
Yes
Check the connections of the
reactor (L) in wiring diagram
Replace AP1 circuit board
I reactor wiring normal?
Connect wiring
according to the wring
diagram
No
Restart the unit,
is the malfunction
corrected?
No
Yes