King Series
-
46
-
active, indoor motor runs as the blowing surplus heat condition. If T
set
+2 < T
indoor
< T
set
+4 ,
keeps the original state.
c. If T
indoor
T
set
+ 3
, select cooling mode, the set temp. is 25 , If T
indoor
T
set
-1
, compressor,
outdoor motor stop, 15 seconds later indoor motor runs at the set speed.
d.Cooling & heating AUTO mode: in AUTO mode, when the machine is switched from heating
mode to the other modes, reversing valve becomes inactive in 60 seconds.
Cooling only AUTO mode: there is no heating function in this mode.
(3)protections
It is same as the one in cooling or heating mode, there is only one exception , the compressor
doesn’t have at least 5 minutes protection.
E. other controls
1.SWING mode
a. When it is active, the louver returns to position O, close the air outlet.
b. When machine works, it turns to the max. Air output position D, then returns back to position
L to stand by (position L is the horizontal place mentioned before).
c. In swing state, the louver swings between position L and position D.
d. When the machine is switched off, it is back to position O.
O
D
D
2.beeper
When PCB becomes active or receives the signal from the remote controller , the beeper will
beep.
3.indication lamps
it flashes when defrosting begin.
4.multi-step switch .
a. If the switch is in AUTO position, the machine will run at the AUTO mode, if there is a signal
from remote controller, it will run according to the signal .
b. If the switch is in TEST position, the machine will run at the COOL mode, indoor motor will run
at high speed , swing motor will run according to SWING mode. If there is a signal from
remote controller, it will run according to the signal .if the thermostat is open-circuited or
short-circuited , the beeper will alarm at the frequency 2 HZ .