10
Technical Information
Service Manual
Outdoor Unit
Model of Outdoor Unit VIR36HP230V1CO
LIVS36HP230V1CO
Outdoor Unit Product Code CB432W08100 CB432W20300
Compressor Manufacturer/Trademark
ZHUHAI LANDA
COMPRESSORCO., LTD.
ZHUHAI LANDA
COMPRESSORCO., LTD.
Compressor Model QXAS-D32zX090A QXAS-D32zX090A
Compressor Oil FV50S FV50S
Compressor Type Rotary Rotary
Compressor Locked Rotor Amp (L.R.A) 67 67
Compressor RLA A 17.5 17.5
Compressor Power Input W 4150 4150
Overload Protector
1NT11L-6233/HPC 115/95/KSD
115oC
1NT11L-6233/HPC 115/95/KSD
115oC
Throttling Method Electron expansion valve Electron expansion valve
Operation temp ºF 61~86 61~86
Ambient temp (cooling) ºF 0~109 0~109
Ambient temp (heating) ºF -4~75 -4~75
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Pipe Diameter inch Φ5/16 Φ5/16
Rows-n Gap inch 2-1/16 2-1/16
Coil Length (LXDXW) inch 37X1 3/4X30 37X1 3/4X30
Fan Motor Speed rpm 890 890
Output of Fan Motor W 170 170
Fan Motor RLA A 0.73 0.73
Fan Motor Capacitor μF / /
Air Flow Volume of Outdoor Unit CFM 2589 2589
Fan Type Axial-ow Axial-ow
Fan Diameter inch Φ21 21/32 Φ21 21/32
Defrosting Method Automatic Defrosting Automatic Defrosting
Climate Type T1 T1
Isolation I I
Moisture Protection IPX4 IPX4
Design Pressure(High) PSIG 550 550
Design Pressure(Low) PSIG 240 240
Sound Pressure Level (H/M/L) dB (A) 65/-/- 65/-/-
Sound Power Level (H/M/L) dB (A) 75/-/- 75/-/-
Dimension (WXHXD) inch 39 1/2X31 7/64X16 13/16 39 1/2X31 7/64X16 13/16
Dimension of Carton Box (LXWXH) inch 42 1/2X19X33 42 1/2X19X33
Dimension of Package (LXWXH) inch 42 21/32X19 13/64X33 21/32 42 21/32X19 13/64X33 21/32
Net Weight Ib 158.8 158.8
Gross Weight Ib 169.8 169.8
Refrigerant R410A R410A
Refrigerant Charge oz 91.71 91.71
Connection
Pipe
Length ft 24.6 24.6
Gas Additional Charge oz/ft 0.5 0.5
Outer Diameter Liquid Pipe inch 1/4 1/4
Outer Diameter Gas Pipe inch 5/8 5/8
Max Distance Height ft 32 3/16 32 3/16
Max Distance Length ft 98 27/64 98 27/64
Note:The connection pipe applies metric diameter.
The above data is subject to change without notice; please refer to the nameplate of the unit.