EasyManua.ls Logo

Gree LSQWRF130M/N-M - 4-Way Valve Disassembly and Assembly

Gree LSQWRF130M/N-M
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AIR COOLED SCROLL CHILLER MAINTENANCE
40
Disassembly and Assembly of 4-way valve
Remarks: Before removing the 4-way valve, cut off the power and reclaim the refrigerant;
Step Illustration Handling Instruction
1. Record the
direction of the
4-way valve before
welding it. Do not
refer to the other
system.
z Record the direction of
4-way valve before
removing it.
z remove the coil.
z Wrap the 4-way valve
with wet cloth before
welding so that it is
complete and can be
analyzed in the future.
z Remove the 4-way valve.
2. Clean the system,
replace the 4-way
valve of the same
model. The piping
should be the same
as it is before
removal.
z the new 4-way valve
should be the same as the
replaced one. If not, it
should be confirmed by
the professionals.
z wrap the the 4-way valve
with wet cloth.
z Connect the the 4-way
valve with the four
connecting pipe according
to the original direction.
z Connect the pipe by
welding.
z Charge nitrogen when
welding.
3. Pressurize and
vacuumize the
system. Recharge
the refrigerant.
z Ensure that the vacuum
degree is -1.0bar. The
period for vacuuming is
longer.
z The name and wight of
the charged refrigerant
should comply with the
reqiurement marked on
the nameplate.