DC Inverter U-Match Series Cassette Type Unit
28
1
2
A
1
2
3
During the installation, distance from soft drain
pipe to the gasket is A mm when the bolt is
tightened. It is not allowed to apply PV
C or
other related glue in the joints of two ends of
drain pipe.
Metal clamp (accessory)
Insulation sponge (accessory)
Insulate the pipe clamp and the
drain hos
e using heat insulation
sponge.
Metal clamp
Drain hose (accessory)
Grey tape (accessory)
Indoor Unit
A mm
GUD35T/A-S
≤12
GUD50T/A-S
≤12
GUD71T/A1-S
≤15
GUD71T/A-S
≤15
GUD100T/A-S
≤15
GUD125T/A-S
≤15
GUD140T/A-S
≤15
GUD160T/A-S
≤15
3.2.6.2 Outdoor Side Drainage Pipe
(1) If the outdoor unit is underneath the indoor unit, arrange the pipeline
according to the following diagram.
1) Drain hose should be placed on the ground and its end should not be
immersed into water. The whole pipeline should be supported and
fixed onto the wall.
2) Wind the insulating tape from bottom to top.
3) The whole pipeline should be wound with insulating tape and fixed
onto the wall with saddles.