Growatt 3600MTL-S - AC Connection Plug Assembly and Wire Sizing

Growatt 3600MTL-S
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2423
2. Remove the parts of the AC connection plug from the accessory bag.Guide the
pressure screw, sealing ring, threaded sleeve over the AC cable.
Max. cable length
33m
42m
28m
36m
Wire suggestion length:
If the installation requires,the ground terminal can be used to connect a second
protective conductor or as a equipotential bonding.the second protective poing
local as figure below.
3. Insert the stripped and bared conductors L,N,PE into the screw terminals with
sign L,N,PE on the socket element and tighten the screws firmly.
Conductor cross
section
5.2 mm² 10AWG
6.6 mm² 9AWG
6.3 connecting the second protective conductor
Growatt
3600MTL-S
Growatt
4200MTL-S
Growatt
3000MTL-S
40m
50m
Max. cable length
26m
33m
Conductor cross
section
5.2 mm² 10AWG
6.6 mm² 9AWG
Growatt
5000MTL-S
Growatt
5500MTL-S
24m
30m
Growatt
2500MTL-S
48m
60m
4.Push the threaded sleeve into the socket element; screw the pressure screw
tightly onto the threaded sleeve;
5.Finally, insert the AC connection plug into the AC connection receptacle on the
inverter.
socket elementthreaded sleeve
stealing ring
pressure screw
Lock the housingUnlock the housing