6.9 Operating Conditions.
Electrical supply: 230 V +10 /-6%, 50 Hz
Electrical load:
Model
Power (Watts)
Full Load current (Amps)
PHT-N130/PHT-N230
28 W
0.12 A
PHT-D125/PHT-D225
410 W
1.83 A
PHT-D150/PHT-D250
900 W
3.94 A
PHT-F125/PHT-F225
410 W
1.83 A
PHT-F150/PHT-F250
900 W
3.94 A
PHT-F180/PHT-F280
1150 W
5.2 A
PHT-T225/PHT-V225
410 W
1.83 A
PHT-T250/PHT-V250
900 W
3.94 A
Quiescent All models
15 W
0.07 A
Pollution Degree: 3 Noise level: <70 dB(A) at full speed
Liquid temperature range: +1°C to +60°C Ambient temperature: From +1°C to 40°C
Relative humidity: 95% (non-condensing)
Usage: Indoor (Outdoor, subject to restrictions found)
Type of protection: Class 1 (earthed) equipment
Equipment type: Stationary, fixed equipment
Construction type: Fixed construction, no moveable parts
EMC Environment: B (light industrial, commercial and residential)
Inlet pressure max: 3 bar
6.10 Wall Fixings.
All units must be mounted/stood in the vertical position.
The PHT-N and PHT-D units are suitable for wall fixing.
The wall fixing dimensions are given below.
Fig 5. Wall fixing dimensions
Refer to the Product weight table also.